Connect The Drain Pipe - Trane 18, 24, 30, 36, 24, 42, 48 Installation Manual

Table of Contents

Advertisement

Table7-6
MODEL
A
Unit
18~24
595
30~36
624
48
646
Prepare a polyviny chloride with 21mm inner diameter
Fasten the tube to the drain hose with an adhesive and the
field-supplied clamp. The drain piping must be performed with
a DOWN-SLOPE pitch of 1/25 to 1/100
Connect a siphon, as shown in figure below
Slope 2 %

8. CONNECT THE DRAIN PIPE

Install the drainpipe of the indoor unit
You can use a polyethylene tube as the drainpipe
(out-dia.37-39mm, in-dia.32mm). It could be bought at local
market or from your dealer.
Set the mouth of the drainpipe onto the root of the body's
pump-pipe, and clip the drainpipe and the out-let pipe sheath
(fittings) together firmly with the out-let pipe clasp (fitting).
The body's pump pipe and the drainpipe (especially the
indoor part) should be covered evenly with the out-let pipe
sheath (fittings) and be bound tightly with the constrictor to
prevent condensation caused by entered air.
To prevent water from flowing backwards into the air
conditioner while the air conditioner stops, please lean the
drainpipe down toward outdoor (outlet-side) at a degree of
over 1/ 50. And please avoid any bulge or water deposit. (
Refer to Fig.5-17.a in the figure page)
Do not drag the drainpipe violently when connecting to
prevent the body from being pulled. Meanwhile, one
supportpoint should be set every 1~1.5m to prevent the
drainpipe from yielding
(Refer to Fig.5-17a in the figure page)
Or you can tie the drainpipe with the connecting pipe to fix
it.
(Refer to Fig.5-17.c in the figure page)
In the case of prolonged drainpipe, you had better tighten its
indoor part with a protection tube to prevent it from loosing.
mm
B
1200
1381
1385
75
Plug
Fig.7-11
If the outlet of the drainpipe is higher than the body's pump
joint, the pipe should be arranged as vertically as possible.
And the lift distance must be less than 200mm, otherwise the
water will overflow when the air conditioner stops. (Refer to
Fig.5-18 in the figure page)
The end of the drainpipe should be over 50mm higher than
the ground or the bottom of the drainage chute, and do not
immerse it in water. If you discharge the water directly into
sewage, be sure to make a U-form aquaseal by bending the
pipe up to prevent the smelly gas entering the house through
the drain pipe.
Drainage test
Drainage test
Check whether the drainpipe is unhindered.
New built house should have this test done before paving
the ceiling.
1
Remove the test cover, and stow water of about 2000ml to the
water receiver through the stow tube. ( Refer to Fig.5-18 in the
figure page)
2
Turn on the power, and operate the air conditioner under the
"COOLING" mode. Listen to the sound of the drain pump.
Check whether the water is discharger well (a lag of 1min is
allowed before discharging, according to the length of the drain
pipe), and check whether water leaks from the joints.
3
Stop the air conditioner, turn off the power, and reset the test
cover to its original position.
The drain plug is used to empty the water-receiver for
maintenance of the air conditioner. Please stuff it
imposition at all times during operation to avoid leakage.
Install the drain joint of the outdoor unit
Fit the seal into the drain joint, then insert the drain joint into the
base pan hole of outdoor, rotate 90° to securely assemble them.
Fit the seal into the drain joint, then insert the drain joint into the
base pan hole of outdoor, rotate 90° to securely assemble them.
Connect the drain joint with an extension drain hose (Locally
purchased), in case of the condensate draining off the outdoor
unit during the heating mode.
Seal
Drain joint
The base pan
of outdoor unit
.
All the pictures in this manual are for explanation
purpose only. They may be slightly different from the air
conditioner you purchased(depend on model).The
actual shape shall prevail.
NOTE
The base pan hole
of outdoor unit
Seal
Drain
joint
Fig.8-1
NOTE
installation manual
15