Bustibles - Schwank sportSchwank Series Installation And Owner's Manual

Table of Contents

Advertisement

7. MINIMUM CLEARANCES TO COMBUSTIBLES
FIGURE 4: MINIMUM CLEARANCES TO COMBUSTIBLE
A
R
B
TABLE 3: MINIMUM CLEARANCES TO COMBUSTIBLE
ABOVE
sportSchwank
A
In. [cm]
10
24" [61] 8" [20] 66" [91] 66" [170] 18" [46] 30" [76]
15
24" [61] 8" [20] 66" [91] 66" [168] 18" [46] 30" [76]
20
24" [61] 8" [20] 70" [91] 70" [178] 18" [46] 36" [91] 100" [254]
30
24" [61] 8" [20] 74" [91] 74" [188] 18" [46] 42" [107] 105" [267]
The structure, materials, or items in proximity to, or stored under the
heater will be subjected to radiant heat and could be seriously damaged.
The clearances to combustible material represent the minimum distanc-
es that must be maintained between the outer heater surface and a
nearby surface so that a surface temperature of 90F°(50C°) above ambi-
ent is not exceeded.
It is the installer's responsibility to ensure that building materials with a
low heat tolerance which may degrade at lower temperatures are pro-
tected to prevent degradation.
Angle Mounted
1° to 30°
F
Angle Mounted 1° to 30°
REAR
BELOW
R
B
In. [cm]
In. [cm]
Horizontal
S
FRONT
TOP
F
T
In. [cm]
In. [cm]
Page 9
T
S
U
Horizontal
SIDES
UNDER
S
U
In. [cm]
In. [cm]
90" [229]
96" [244]
sportSchwank Manual
IM080731
RD: APR 2019
RL: 01B

Advertisement

Table of Contents
loading