Omron SYSMAC CPM2B Operation Manual page 40

Programmable controller
Hide thumbs Also See for SYSMAC CPM2B:
Table of Contents

Advertisement

Specifications
Transistor Outputs (Sinking or Sourcing)
Item
Max. switching
OUT01000 and OUT01001:
capacity
OUT01002 and up:
Leakage current
0.1 mA max.
Residual voltage
1.5 V max.
ON delay
OUT01000 and OUT01001:
OUT01002 and up:
OFF delay
OUT01000 and OUT01001:
OUT01002 and up:
Fuse
1 fuse/output (cannot be replaced by user)
Sinking Outputs
Circuit configuration
Caution
!
28
Note The service life of the CPM2B's relay output contacts shown in the table as-
sumes the worst conditions. The following graph shows the results of OMRON's
service life tests at a switching rate of 1,800 times/hour.
4
Life (x 10
)
4.5 to 30 V DC, 0.2 A/output (See note 1.)
4.5 to 30 V DC, 0.3 A/output (See note 1.)
20 µs max.
0.1 ms max.
40 µs max. for 4.5 to 26.4 V, 10 to 100 mA
0.1 ms max. for 4.5 to 30 V, 10 to 200 mA
1 ms max. for 4.5 to 30 V, 10 to 300 mA
Note When using OUT01000 or OUT01001 for pulse outputs, connect a dummy re-
sistor as required to bring the load current between 0.01 and 0.1 A. If the load
current is below 0.01 A, the ON-to-OFF response time will be too long and high-
speed pulses will not be output.
Do not apply voltage in excess of the maximum switching capacity to an output
terminal. It may result in damage to the product or fire.
120 V AC, resistive load
24 V DC, τ = 7 ms
120 V AC, cosφ = 0.4
240 V AC, cosφ = 0.4
24 V DC/240 V AC, resistive load
Contact current (A)
Specification
Output LED
OUT
Internal
OUT
circuits
COM (–)
Section
Switching rate:
1,800 times/hour
24 V DC
2-1