RGU-10 B, RGU-10 B RCM REVISION LOG Table 1: Revision log� Date Revision Description 11/20 M087B01-03-20A Nueva versión SYMBOLS Table 2: Symbols� Symbol Description In compliance with the relevant European directive. In accordance with the CMiM directive. In accordance with the UKCA directive (UK Conformity Assessed) The device complies with the 2012/19/EC European directive.
2.- DESCRIPTION OF THE PRODUCT RGU-10 B is a electronic type B earth leakage current protection and monitoring relay. It has 2 programmables outputs relays: main trip relay and prealarm relay. It has one free voltage input for external TRIP/RESET.
Page 7
RGU-10 B, RGU-10 B RCM There are 2 models of the device: RGU-10 B, protective device (IEC 60947-2 M). RGU-10 B RCM monitoring device (IEC 62020). Main features: - Measuring in true effective value (TRMS) - Type B differential (IEC 60947-2 Annexed M) - Insulation against transients (IEC 61008.1)
The RGU-10 B device must be installed by authorised and qualified staff. Disconnect the device from the mains and disconnect the measuring devices before handling, chang- ing the connections of or replacing the device.
RGU-10 B, RGU-10 B RCM 3�2�- INSTALLATION While the device is connected, the terminals, opening the cover or removing ele- ments can expose parts that are hazardous to the touch. The device must not be used until the installation process is complete.
RGU-10 B, RGU-10 B RCM 3�- The front frame is attached to cover the mounting points. 4�- Three green pressure tabs on the side runners of the base are attached. 5�- The device is mounted in the hole in the panel with the adapter.
RGU-10 B, RGU-10 B RCM 4�2�- DESCRIPTION OF THE DEVICE The front of the equipment which is formed by the display, buttons and LEDs, is protected with a seal- able plastic cover which has the appropriate holes to access the RESET, TEST and PROG/PAG keys.
RGU-10 B, RGU-10 B RCM 4�4�- KEYBOARD FUNCTIONS The device has 7 keys, Figure 8 1�- Keys accessible with sealed cover and tool RESET, Starts the device after a trip. TEST, Carries out a trip to check the proper operation of the relay.
RGU-10 B, RGU-10 B RCM If the device trips through any event, the screen’s background changes to red and the reason for the trip is displayed. Figure 9: Display RGU-10B� Display messages by device trip, Table 6 Table 6: Display messages by device trip�...
Page 18
RGU-10 B, RGU-10 B RCM Trip sensitivity Trip delay Instant current leakage Contact polarity Prealarm reclosing Prealarm con guration Figure 11: Descripción display� In normal operating status the display shows the following parameters associated with the earth leak- age protection, Table 8�...
After a certain time the device will carry out a test to detect the presence of the sensor or associated earth leakage transformer. Also the “ERRt” error message will permanently appear on the RGU-10 B display. A short-circuit in the transformer secondary will also be detected as an error.
Page 20
RGU-10 B, RGU-10 B RCM Figure 13: Remote trip� When it is remotely reset (input terminals 1-2, removing the 230 Vac) the device is reconnected with the display backlit in green, LED ON in green as in normal status. Instruction Manual...
RGU-10 B, RGU-10 B RCM 5.- CONFIGURATION 5�1�- ADIRECT SETTING By pressing for a long time on any of the direct setting buttons, Configuration mode is entered and the relay’s setting may be changed. While in Configuration mode if any other direct function is used (Id, td, Std/+ y Auto), the parameter for the displayed relay can also be set.
RGU-10 B, RGU-10 B RCM 5�1�3�- POSITIVE SECURITY SETTING OF THE MAIN RELAY “Std”, contacts are on standby, terminals 14 - 15 (NC) and 13 - 15 (NO). “+”, contacts change status on powering the device, the + sign is displayed. Terminals 14 -15 (NO) and 13 -15 (NC).
Page 23
RGU-10 B, RGU-10 B RCM 5�1�4�2�- Prealarm time setting This is in terms of the program value in the main relay. Pressing td enters to change the values. Press- ing td changes the values: 100, 200, 300, 400, 500, 750 ms, 1, 5 and 10 s�...
RGU-10 B, RGU-10 B RCM 6.- TECHNICAL FEATURES Power supply AC Rated voltage 230 V ~ ± 20% Frequency 50 - 60 Hz Consumption 6 VA Installation category CAT III 300 V Power supply DC Rated voltage 24 ... 125 V ± 20%...
Page 25
RGU-10 B, RGU-10 B RCM Environmental features Operating temperature -10ºC ... +50ºC Storage temperature -20ºC ... +55ºC Humidity (without condensation) 5 ... 95% Maximum altitude 2000 m Assembled device: IP41 (Front) Protection degree Unmounted device: IP20 (Sides and back cover)
RGU-10 B, RGU-10 B RCM 7.- TECHNICAL SERVICE In the case of any query in relation to device operation or malfunction, please contact the CIRCUTOR, SA Technical Support Service. Technical Assistance Service Vial Sant Jordi, s/n, 08232 - Viladecavalls (Barcelona) Tel: 902 449 459 ( España) / +34 937 452 919 (outside of Spain)