Minimum Enclosure Clearances - Napoleon Galaxy Series Manual

Outdoor gas fireplace
Hide thumbs Also See for Galaxy Series:
Table of Contents

Advertisement

10
GSS48 (ONE SIDED)

Minimum Enclosure Clearances

!
WARNING!
cement board, ceramic tile, marble, paint etc. When adding finishing materials to the appliance. Do
not use wood or drywall.
!
WARNING!
and connected to the gas supply in order to safely turn off the burner.
36"
(914mm)
minimum
to ceiling.
60 3/4"
(1543mm)
minimum
to ceiling.
24 3/4" (629mm)
Including 1/8"
(3mm) clearance
per side.
6"
(152mm)
6"
(152mm)
minimum to
floor
NOTE!
Ensure top of cabinet is closed to
prevent rain and debris from falling on top of
the appliance.
www.napoleon.com
Use only non-combustible materials (certified to ASTM E-136) such as steel studs,
You must have clear and easy access to the on/off valve AFTER the appliance is installed
NON COMBUSTIBLE
6"
(152mm)
50 3/4" (1289mm)
(Including 1/8" (3mm)
clearance per side)
36"
(914mm)
minimum
to ceiling.
6"
(152mm)
minimum to
floor
1 1/2"
(38mm)
All material in shaded
Combustible. (including
framing, sheeting and
Certified to ASTM E-136
Nailing Tabs (4 per side)
6"
(152mm)
Gas and electrical lines protude from the
bottom of the appliance located on the
right side.
All material in shaded
area must be Non
Combustible. (including
framing, sheeting and
finishing materials).
Certified to ASTM E-136
1/2"(13mm)
Cement Board
6"(152mm)
Steel Stud
6" (152mm)
(Minimum
clearance to
combustibles)
area must be Non
finishing materials).
N415-0346-AU FEB 23.21