3.2
MINIMUM ENCLOSURE CLEARANCES
WARNING
!
RISK OF FIRE!
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., AS LONG AS THE FINISHING MATERIAL DOES NOT GO
BELOW THE SPECIFIED DIMENSION AS ILLUSTRATED. AS AN ALTERNATIVE, YOU CAN FINISH THE
APPLIANCE WITH DRYWALL, SEE DIAGRAM BELOW FOR DETAILS.
FACING AND / OR FINISHING MATERIAL MUST NEVER OVERHANG INTO THE APPLIANCE OPENING.
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT MEASURED FROM THE APPLIANCE
BASE.
COMBUSTIBLE
6 1/4"
4 1/2"
NON-
COMBUSTIBLE
39 1/4"
1"
The appliance requires a minimum enclosure height of 39 1/4". For temperature requirements, the enclosure
space around and above the appliance must be left unobstructed.
W415-0807 / 06.25.09