Greenheck DS-M Installation, Operation And Maintenance Manual page 16

High volume, low speed ceiling fans
Table of Contents

Advertisement

®
Gripple
Hardware (Optional)
IMPORTANT: Guy wires must be installed 45º to 60º
from vertical to ensure proper functioning.
Components required from Bag # 915067:
• Guy Wire Clamp Assembly (4)
• Guy Wire Clamp Bolt (4)
• Quick Link (8)
• 20 ft. Guy Wire (4)
®
• No. 4 Gripple
Connector (4)
• Turnbuckle (4)
Hardware/Tools Needed (Not Included):
• Adjustable Wrench
• Level
• 1/16 in. Allen Wrench (optional)
GUY WIRE
1. Secure guy wire clamps to the building structure
using the guy wire clamp bolts. Attach guy wires
TURNBUCKLE
®
to the eyelets on the guy wire clamp assemblies
using (4) supplied quick links.
2. Insert the loose end of each guy wire into a No. 4
Gripple connector until a length of wire is pushed
through the connector. Insert the loose end of the
guy wire through the end of the turnbuckle and
push back through the No. 4 Gripple connector to
close the loop.
3. Attach all (4) turnbuckles to the guy wire
attachment ring located on the downtube using
(4) supplied quick links. Pull the loose end of each
guy wire through the No. 4 Gripple connector until
each guy wire is taut.
DOWNTUBE & MOUNT ASSEMBLY
GUY WIRE ATTACHMENT RING
16
High Volume, Low Speed Ceiling Fans
GUY WIRE CLAMP BOLT
GUY WIRE CLAMP ASSEMBLY
QUICK LINK
GUY WIRE
45º to 60º
GUY WIRE
No. 4 GRIPPLE CONNECTOR
TURNBUCKLE
QUICK LINK
4. Place a level against the downtube and tighten all
(4) turnbuckles by hand in a crisscross pattern until
the guy wires are tight and the fan is level.
NOTE: When leveling the fan, place the level against
the downtube in-between two neighboring guy wires
to simplify the leveling process. The level should also
be moved around the circumference of the downtube
periodically to ensure that the fan is level in all
directions.
5. Cut or organize excess guy wires to ensure that
they do not interfere with fan rotation.
NOTE: If necessary, the guy wires can be loosened by
inserting the long end of a 1/16 in. allen wrench into
either of the pin holes on the No. 4 Gripple connector
and pulling the cable in the opposite direction of the
arrow marked on the Gripple connector.
GUY WIRE CLAMP BOLT
GUY WIRE CLAMP ASSEMBLY
QUICK LINK
GUY WIRE
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ds-m3Ds-m6

Table of Contents