Shutting down the inverter on the WebUI.
On the system WebUI, choose Monitoring > Control, and click Inv. OFF. After confirmation,
the inverter is shut down.
6.2
Powering Off a Single UPS
Turn off the system output switch (Q5).
Turn off mains input circuit breaker 1 (Q1-1), mains input circuit breaker 2
(Q1-2), bypass input switch (Q2), output circuit breaker 1 (Q5-1), and output
circuit breaker 2 (Q5-2) of the UPS.
Turn off the battery string circuit breaker of each power unit. If there are
multiple battery strings, turn off the general circuit breaker between
battery strings and the UPS and then turn off the circuit breaker for each
battery string.
Turn off the upstream bypass and mains input switches for the UPS.