1MRK 502 073-UEN Rev. J
IEC15000023 V1 EN-US
4.
Click Start editing signal value for forcing on the tool bar.
IEC15000024 V1 EN-US
The Signal Monitoring menu changes and indicates the forcing values that can be edited.
IEC15000025 V1 EN-US
5.
Select and edit the values.
6.
Click Acknowledge and send.
IEC15000026 V1 EN-US
This commits the values to the IED and exits the editing session.
7.
Click Cancel to abort the changes and revert back to actual IED values.
IEC15000032 V1 EN-US
Generator protection REG670
Commissioning manual
Regardless if the forcing changes are commited or canceled, the forcing is still
active.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 12
Testing IED operation
127