Cable Sizing For Outdoor Unit - Samsung Electronics DVM Series Technical Manual

Table of Contents

Advertisement

7-2. Cable sizing for outdoor unit

Outdoor unit
Power
Supply
-
380V-
415~/
50Hz
-
380V-
415~/
50Hz
380V-
415~/
50Hz
208V-
230~/
60Hz
308V/
60Hz
380V-
415~/
50Hz
208V-
230~/
60Hz
The power cable is not supplied with air conditioner.
IMPORTANT : All power supply cables/interconnection cables and communication cables must be type HOS-RN-F (at least).
Power Supply
3 Phase
Max/Min
Power
MCCB
ELB
Cable Length
(V)
-
-
-
-
4.0mm
2
,
HOS-RN-F,
or less
Frame:50A
3Wires
456/342
30A
Trip:30A
6.0mm
2
,
16m~20m
HOS-RN-F,
3Wires
-
-
-
-
4.0mm
2
,
HOS-RN-F,
or less
Frame:30A
3Wires
456/342
20A
Trip:20A
6.0mm
2
,
16m~20m
HOS-RN-F,
3Wires
4.0mm
2
,
HOS-RN-F,
or less
Frame:50A
3Wires
456/342
30A
Trip:30A
6.0mm
2
,
16m~20m
HOS-RN-F,
3Wires
-
253/187
-
-
-
4.0mm
2
,
HOS-RN-F,
or less
3Wires
Frame:50A
418/342
30A
Trip:30A
6.0mm
2
,
16m~20m
HOS-RN-F,
3Wires
8.0mm
2
,
HOS-RN-F,
or less
Frame:75A
3Wires
456/342
50A
Trip:50A
14.0mm
2
,
20m~50m
HOS-RN-F,
3Wires
14.0mm
2
,
HOS-RN-F,
3Wires
Frame:100A
75A
253/187
Trip:75A
22.0mm
2
,
HOS-RN-F,
3Wires
29
Single Phase
Power
Max/Min
MCCB
ELB
Supply
(V)
208-
-
253/187
25A
25A
230V~
/60Hz
16m
220-
240V~
264/198
16A
16A
/50Hz
208-
-
230V~
253/187
-
-
/60Hz
16m
264/198
16A
16A
16m
220-
264/198
16A
16A
240V~
/50Hz
-
208-
-
230V~
-
-
/60Hz
-
16m
242/198
16A
16A
220V
20m
220-
264/198
20A
20A
240V~
/50Hz
208-
253/187
20A
20A
230V~
/60Hz
Commu-
nication
Earth
Cable
Cable
Power
(HOS-RN-
F, 2wires)
Cable
2.0mm
2
,
CV, 3Wire
2.0mm
2
,
HOS-RN-F,
2Wires
2.0mm
2
,
HOS-RN-F,
2Wires
1.5mm/ ",
0.75~
HOS-RN-F,
1
1.25mm
2
16
1Wire
2.0mm
2
,
HOS-RN-F,
2Wires
2.0mm
2
,
HOS-RN-F,
2Wires

Advertisement

Table of Contents
loading

Table of Contents