3-3. Communication error on all PBA within the outdoor unit C-Box,
communication cable error. (E-205)
Outdoor unit Display
Indoor unit Display
Judgement Method
Cause of problem
Did the communication
connector break away
from the PCB?
Is inverter PCB CN32
and Fan PCB CN12
connector accurately
connected?
Is FAN PCB LD22, 32 ashes?
Replace main PCB.
36
Duct, Cassette (1 / 2Way), Console, Ceiling
Operation
×
Cassette (4Way / Mini 4Way)
Operation
×
Duct, Cassette (1/2 Way), Console, Ceiling
Operation
×
Yes
Yes
E-205
Defrost
Timer
×
Defrost
Timer
Timer
Turbo
×
: ON
: Flash ×: OFF
※ ●
Restart operation after connecting the inverter
PCB2 CN31(when the Comp. applied one :Inverter PCB1)
No
connector. (Check the 3, 4 Pin short)
* When performing the connector work, Pleaseturn off
the main power .
Check the Inverter PCB1 CN32, CN91 and Fan PCB
No
CN12 Communication wire / Connector .
* When performing the connector work, Please
turn off the main power.
Check the Main PCB : Main PCB TX circuit Inspection
No
* When performing the connector work, Please
turn o the main power
Fan
Filter / MPI
×
Filter
×
24°C
27°C
×
Samsung Electronics