. Installation
1. Product
(2) Outdoor unit
1) Onward
24" or more
12" or more
The air inlet faces toward the wall.
2) Upward (7.5HP or less)
If there are no obstacles around the unit...
Max. height of obstacle
- Front side : 5ft. or less
- Air inlet side : 2ft. or less
- Right/Left side : No limit
If there is an obstacle around the unit...
If an obstacle in front of the outdoor unit is higher than
5ft., the half of additional height should be
added to the S1.
If an obstacle behind the outdoor unit is higher than 2ft.,
the half of additional height should be added to the S2.
Strong wind
Roof top
20" or more
Space for piping
and wining
12 or more
Front
4 or more
4 or more 4 or more
20 or
more
12 or more
Front
4 or more
4 or more
20 or
more
6
12" or more
12" or more
The air outlet faces toward the wall.
12 or more
20 or more
4 or more
Front
4 or more
4 or more
20 or more
8 or more
Front
S1
20" or more
Space for piping
and wining
Unit : inch
4 or more
4 or more
4 or more
8 or more
S2