. Outdoor unit
1. Unit selection (based on cooling load)
1-1. Indoor unit selection
Select the indoor unit based upon cooling load and unit capacity. (The indoor unit capacity should larger than the load.)
Indoor units can be of different capacities, however total capacity
must be checked against the outdoor unit capacity table.
1-2. Outdoor unit selection
Allowable combinations are described on the indoor unit combination total capacity index table.
For a standard indoor unit and outdoor unit combination, select the nearest value of the total
indoor unit capacity index that is less than a 100% outdoor unit combination capacity index.
Indoor unit combination total capacity index
outdoor unit
RVMH060GBM0
RVMH100GAM0
RVMH100FAM0
The system enables the connection of indoor units with a total capacity of between 50 to 130% of that of the
corresponding outdoor unit but where this capacity ratio exceeds 100% then the actual capacity of each indoor
unit will fall a little short of its individual rated capacity when all the units are operated simultaneously. (Except
Middle East models)
Indoor unit capacity index
- 50Hz
Unit size
capacity index
- 60Hz
Unit size
capacity index
indoor unit combination rate
130%
120%
110%
100%
20.8
19.2
17.6
16.0
36.4
33.6
30.8
28.0
36.4
33.6
30.8
28.0(ISO)
020
026
035
052
2.0
2.6
3.5
5.2
020
032
040
052
2.0
3.2
4.0
5.2
Ι Λ
2
90%
80%
70%
60%
14.4
12.8
11.2
9.6
25.2
22.4
19.6
16.8
25.2
22.4
19.6
16.8
060
070
082
105
6.0
7.0
8.2
10.5
060
072
083
105
6.0
7.2
8.3
10.5
50%
8.0
14.0
14.0
128
12.8
128
12.8