6.4
Pressure switch adjustment
6.4.1
Oil pressure switch
The pressure switch 5)(Fig. 5 on page 12) is adjusted in the
factory at 3 bar. If the light oil pressure reaches this value in the
return duct, the pressure switch stops the burner.
The burner restarts automatically if the pressure goes back to
less than 3 bar after stopping.
If the burner is fed by a loop circuit with a pressure of Px, the
pressure switch must be adjusted at Px + 3 bar.
To adjust the pressure switches, use a tool to operate the
adjustment screw, see Fig. 34.
Start-up, calibration and operation of the burner
29
GB
20079898
Fig. 34
20166451