alarm delay
Alarm delay for flow guard.
alarm class
This setting decides whether the brine flow alarm should be an A-alarm or a
B-alarm.
3�6�2 Heating
Control curve supply temp
A set point curve that determines the primary supply temperature set point
at different outdoor temperatures. Each point in the curve can be edited, and
there is a setting Curve offset that provides parallel displacement of the whole
set point curve.
room temp feedback
This setting activates or disables room temperature feedback.
room set point
Room temperature set point, used only when room temperature feedback is
activated.
Curve room temp feedback
A curve that decides how much the set point curve is to be adjusted at diffe-
rent room temperature deviations from the set point.
Calendar room temp
A week schedule that decides at what times the room temperature set point
should be adjusted. Can be used to lower temperatures at night. The setting
Calendar offset decides how much the room set point is to be adjusted when
the week schedule is active.
max system temp
The highest value allowed for the primary supply set point.
min system temp
The lowest value allowed for the primary supply set point.
Integral max limit
The highest positive value allowed for the heat integral.
start hp1
Integral limit for start of the first heat pump.
Delta start hp
Setting that determines how much the integral is allowed to sink between
starts of additional heat pumps.
start extra heater
Determines, after all the heat pumps have been started, how much the inte-
gral is allowed to sink before the extra heater is allowed to start.
Danfoss – 23