Hitachi F350 Hardware Reference Manual

Hitachi F350 Hardware Reference Manual

Virtual storage platform
Hide thumbs Also See for F350:
Table of Contents

Advertisement

Hitachi Virtual Storage Platform F350 and
F370
x
88-07-0
Hardware Reference Guide
This document provides information about the system hardware components and the mechanical and
environmental specifications for the Hitachi Virtual Storage Platform F350 and F370 all-flash arrays.
MK-97HM85016-05
January 2021

Advertisement

Table of Contents
loading

Summary of Contents for Hitachi F350

  • Page 1 Hitachi Virtual Storage Platform F350 and F370 88-07-0 Hardware Reference Guide This document provides information about the system hardware components and the mechanical and environmental specifications for the Hitachi Virtual Storage Platform F350 and F370 all-flash arrays. MK-97HM85016-05 January 2021...
  • Page 2 Materials. “Materials” mean text, data, photographs, graphics, audio, video and documents. Hitachi reserves the right to make changes to this Material at any time without notice and assumes no responsibility for its use. The Materials contain the most current information available at the time of publication.
  • Page 3: Table Of Contents

    16-Gbps Fibre Channel (2-port) board LEDs and connectors....23 Back-end modules..................24 Chapter 3: Drive trays................26 Small form-factor drive tray (DBS/DBSE)............26 SFF with front panel bezel................26 SFF front panel without bezel...............27 Contents Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 4 AC connections.................... 84 Power cable usage guidelines..............86 Three-phase power considerations for racks..........86 Cable management..................86 Appendix E: Power distribution units for Hitachi Universal V2B Rack .......................87 Americas single-phase PDU 1P30A-8C13-3C19UL.P........87 Contents Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 5 Appendix G: Warning labels on the storage system....... 100 CBSS controller....................101 CBSL controller....................102 Small form factor drive tray................103 CBSS/CBSL controller..................103 Battery......................104 Appendix H: Environmental notices..........105 Appendix I: Regulatory compliance..........106 Contents Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 6: Preface

    Preface This guide describes the hardware features and specifications of the Hitachi Virtual Storage Platform F350 and F370 (VSP Fx00 models). Intended audience This document is intended for Hitachi Vantara representatives, system administrators, authorized service providers, or customers who install, configure, and operate the storage system.
  • Page 7: Product Version

    ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Product version This document revision applies to VSP F350, F370 firmware 88-07-0x or later. Release notes Read the release notes before installing and using this product. They may contain requirements or restrictions that are not fully described in this document or updates or corrections to this document.
  • Page 8 Provides helpful information, guidelines, or suggestions for performing tasks more effectively. Caution Warns the user of adverse conditions and/or consequences (for example, disruptive operations, data loss, or a system crash). Preface Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 9: Conventions For Storage Capacity Values

    ) bytes 1 MB 1,024 KB or 1,024 bytes 1 GB 1,024 MB or 1,024 bytes 1 TB 1,024 GB or 1,024 bytes 1 PB 1,024 TB or 1,024 bytes Preface Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 10: Accessing Product Documentation

    Getting help Hitachi Vantara Support Connect is the destination for technical support of products and solutions sold by Hitachi Vantara. To contact technical support, log on to Hitachi Vantara Support Connect for contact information: https://support.hitachivantara.com/en_us/ contact-us.html. Hitachi Vantara Community is a global online community for Hitachi Vantara customers, partners, independent software vendors, employees, and prospects.
  • Page 11: Chapter 1: Overview

    Chapter 1: Overview The Hitachi Virtual Storage Platform F350 and VSP F370 are versatile, rack-mountable all- flash arrays equipped exclusively with flash drives that can be scaled for various storage capacity configurations. To deliver consistent low-latency host response times and high IOPs performance across all host connection ports, conventional hard-disk drives are not supported in the VSP Fx00 models.
  • Page 12 Supports small form-factor drive trays (DBS/DBSE) requiring 2U of rack space and up ■ to 24 2.5-inch HDDs and/or flash drives can be installed Supports system environments with mixed operating systems such as UNIX, Linux, ■ Windows, and VMware Chapter 1: Overview Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 13: Chapter 2: System Controllers

    Each controller includes the following internal components such as a processor, dual in- line cache memory modules (DIMMs), cache flash memory (CFM), battery, and fans. The controller has an Ethernet connection for out-of-band management using Hitachi Device Manager - Storage Navigator. If the data path through one controller fails, all drives remain available to data hosts using a redundant data path through the other controller.
  • Page 14: Cbss Controller Chassis With Front Panel Bezel

    LED might turn off during user maintenance. ALARM LED Off: Normal operation. Red: Processor failure (system might be down). For assistance, contact customer support: https:// support.hitachivantara.com /en_us/contact-us.html. Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 15: Cbss Controller Front Panel Leds (Without Bezel)

    Mode 1097 is set to ON, the WARNING LED does not blink, even if the following failure service information messages (SIM) are issued: 452xxx, 462xxx, 3077xx, 4100xx, and 410100. Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 16: Cbss Controller Rear Panel Leds

    Amber: LAN reset switch was pressed. BACKUP STTS LED Green: Power restoration in progress following power outage. Fast blink green: Restoring. Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 17 Off: Battery is not installed, failure occurred, or firmware is being upgraded. SAS port Port LED Blue: Port link is established. Power supply unit Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 18: Cbss Controller Power Supply Unit Leds And Connectors

    Front-end modules The front-end modules (FEMs), also called channel boards (CHBs), control the transfer of data between the host and cache memory. VSP G130, G/F350, G/F370, G/F700, G/F900 storage systems support Fibre Channel (FC) and iSCSI FEMs for attachment to host servers.
  • Page 19: 10-Gbps Iscsi Board Leds And Connectors (Optical)

    Blue: Normal link status. Blue Blinking: Front-end module is in communication status. iSCSI connectors Connect to Ethernet cables. 10-Gbps iSCSI board LEDs and connectors (copper) Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 20 PORT LED Green: Link connection is established. Blinking: Communication is in progress. Off: No link connection or not ready to communicate. iSCSI connectors Connect to Ethernet cables. Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 21: 8-Gbps, 16-Gbps, Or 32-Gbps Fibre Channel (4-Port) Board Leds And Connectors

    STATUS LED Green: Front-end module is in power-on state. Red: Front-end module can be removed safely. PORT LED Red: Small form-factor (SFF) pluggable can be removed. Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 22 8-Gbps, 16-Gbps, or 32-Gbps Fibre Channel ports (left to right) CHB number Port 1 Port 2 Port 3 Port 4 CHB-1A CHB-1B CHB-1C CHB-1D CHB-1E CHB-1F CHB-1G CHB-1H CHB-2A CHB-2B CHB-2C CHB-2D CHB-2E CHB-2F CHB-2G CHB-2H Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 23: 16-Gbps Fibre Channel (2-Port) Board Leds And Connectors

    4-Gbps or 8-Gbps. Fibre Channel connectors Connect to Fibre Channel cables. Port assignments 16-Gbps Fibre Channel ports (left to right) CHB number Port 1 Port 2 CHB-1A CHB-1B Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 24: Back-End Modules

    The back-end modules (BEMs), also called disk boards (DKBs), control the transfer of data between the drives and cache memory. The back-end module LEDs indicate the operating status of the module. Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 25 Back-end modules Number Item Description PATH 1 connector Connects to a drive tray. PORT LED Blue: Normal link status. Chapter 2: System controllers Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 26: Chapter 3: Drive Trays

    2U (88.2 mm) 2.5 inch (SFF) SFF with front panel bezel Number Item Description POWER LED Green: Drive tray is powered on. READY LED Green: Drive tray is operational. Chapter 3: Drive trays Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 27: Sff Front Panel Without Bezel

    Can be turned on or ■ turned off by the maintenance utility. ALM LED Red: Drive stopped due to a failure and can be replaced. ACT LED Green: Normal operation. Chapter 3: Drive trays Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 28: Sff Rear Panel

    ALARM LED Red: ENC can be replaced. PATH (IN) LED Blue: IN side port is linked PATH (IN) connector Connects to a controller or drive tray. Chapter 3: Drive trays Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 29: Ac Power Supply Unit Leds And Connectors

    The DBSE and DBLE power supply has a Platinum efficiency rating. Number Item Description RDY LED Green: Normal operation. ACI IN LED Green: AC input is operating normally. Chapter 3: Drive trays Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 30 AC power supply unit LEDs and connectors Number Item Description ALM LED Red: Power supply unit can be replaced. Chapter 3: Drive trays Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 31: Chapter 4: Maintaining The Storage System

    The POWER LED changes from green to amber when the process is completed. 3. Verify the POWER LED on the front of the storage system changes from green to amber. Chapter 4: Maintaining the storage system Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 32: Battery Unit

    Up to 24 degrees Celsius 5 years Up to 30 degrees Celsius 5 years Up to 34 degrees Celsius 4 years Up to 40 degrees Celsius 3 years Chapter 4: Maintaining the storage system Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 33: Appendix A: Storage System Parts List

    Appendix A: Storage system parts list The following parts list describes the standard and optional hardware components for the storage systems. For more information about the storage system, contact an Hitachi Vantara sales representative. VSP F350 parts list The VSP F350 includes the following standard and optional components.
  • Page 34 0-24 flash drive DW-F800-1PS16 SFP for 16 Gbps Shortwave 0-16 DW-F800-1PL16 SFP for 16 Gbps Longwave 0-16 DW-F800-1PL32 SFP for 32 Gbps Longwave 0-16 Note: Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 35 7.6 TB, TLC, 12 Gbps, SFF, 0-24 flash drive DKC-F810I-15RMGM 15 TB, TLC, 12 Gbps, SFF, 0-24 flash drive DKC-F810I-30RMGM 30 TB, TLC, 12 Gbps, SFF, 0-24 flash drive Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 36: Drive Tray And Drive Configuration

    30 TB, TLC, 12 Gbps, SFF, 0-24 flash drive Table 10 Optional service processor Model number Part description Quantity HDW2-F850-SVP.P Service processor (Windows 10 Enterprise) Drive tray and drive configuration Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 37: Vsp F370 Parts List

    Model number Part description Quantity DW800-CBSS 2U chassis AC power supply unit Backup module (BKM) Front bezel (2U) Binder SAS cable label DW-F800-RRCB Rail kit Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 38 1.9 TB, MLC/TLC, 12 Gbps, 0-24 SFF, flash drive DKC-F810I-1T9MGM 1.9 TB, TLC, 12 Gbps, SFF, 0-24 flash drive DKC-F810I-3R8MGM 3.8 TB, MLC/TLC, 12 Gbps, 0-24 SFF, flash drive Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 39 Table 13 DBS drive tray components Model number Part description Quantity DW-F800-DBSC 2U chassis AC Power supply unit Front bezel (2U) DW-F800-RRDB Rail kit Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 40 Model number Part description Quantity DKC-F810I-480MGM 480 GB, MLC, 12 Gbps, SFF, 0-24 flash drive DKC-F810I-960MGM 960 GB, MLC, 12 Gbps, SFF, 0-24 flash drive Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 41: Drive Tray And Drive Configuration

    Controller chassis DBS/DBSE Solid-state drive CBSS Data and power cable model list The following tables list the data and power cables available to the storage system. Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 42 5 m SAS cable, including omega clips (2) DW-F800-SCQ10A 10 m SAS optical cable DW-F800-SCQ30A 30 m SAS optical cable DW-F800-SCQ1HA 100 m SAS optical cable Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 43 30 m LC-LC optical cable for optical A-6515-JM50L 50 m LC-LC optical cable for optical A-6515-JM100L 100 m LC-LC optical cable for optical A-6515-JM200L 200 m LC-LC optical cable for optical Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 44 Data and power cable model list Model number Specification A-6515-JM300L 300 m LC-LC optical cable for optical Appendix A: Storage system parts list Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 45: Appendix B: System Specifications

    Appendix B: System specifications The mechanical, electrical, and environmental specifications of the storage system are listed. VSP F350 mechanical specifications The following tables list the system specifications for VSP F350. CBSS controller chassis Item Specification Physical dimension 483 × 813 × 88 mm...
  • Page 46 2. Can be mounted on the RKU rack. For the mounting, special rails for the rack and decoration panels are required separately depending on the number of the mounted storage systems. 3. The value is at maximum level. Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 47 1000 Mbps (iSCSI - Optical) 1000 Mbps (iSCSI - Copper) Number of ports 16/32 Gbps FC (Optical): 16 10 Gbps iSCSI (Optical): 8 10 Gbps iSCSI (Copper): 8 Transferred block size Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 48 However, there is still a possibility of losing data caused by unforeseeable hardware or software failure. Users should always follow recommended best practices and back up all data. Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 49: Vsp F370 Mechanical Specifications

    AC 1,500 V (100mA, 1min) Insulation resistance DC 500 V, 10 MΩ or more VSP F370 mechanical specifications The following tables list the system specifications for VSP F370. Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 50 Physical dimension 482 × 565 × 88.2 mm (W x D x H) (mm) Weight/Mass (kg) 17 kg (Approximate) Start-up time (min) 5 to 8 (min) Required height Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 51 1. When mounting storage system and DBS/DBSE drive trays, the maximum mountable quantity (unit) may vary. 2. Available as spare or data disks. Host interface Item Specification Interface type 16/32 Gbps FC (Optical) Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 52 Up to 75.2º F (24º C) 5 years Up to 86º F (30º C) 5 years Up to 93.2º (34º C) 4 years Up to 104º (40º C) 3 years Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 53 L3 cache memory: 4 MB SDRAM: 1 GB Data assurance method Data bus: Parity Cache memory: ECC (1 bit correction, 2 bit detection) Drive: Data assurance code Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 54: Electrical Specifications

    +6%/-11% intermix drive tray: AC 200-240 +6%/-11% Frequency (Hz) 50/60 ±1 Number of phases, cabling Single-phase with protective grounding Steady-state current 100V/ CBSS: 4.0x2/2.0x2 200V CBSL: 4.0x2/2.0x2 Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 55: Environmental Specifications

    Caution: The following storage system components are not supported in high-temperature environments. Do not operate the following components at temperatures of 40°C or higher: Hitachi Vantara-provided service processor (SVP) server ■ Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 56 (10 ms, half sine wave) Transport (packed) 80 or less (m/s Tipping angle (°) 15° or less (Storage system tips over) (To be measured when installed on leveling bolts.) Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 57 Operating Gaseous contamination should be within ANSI/ISA S71.04-2013 G1 classification levels. Non-operating Recommends the data centers maintain a clean operating environment by monitoring and controlling gaseous contamination. Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 58 Therefore, the rate of the noise occupied by high-frequency content is high. Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 59 The acoustic noise level of 90 dB or less in the operating environment table represents the current operating environment guidelines in which Hitachi storage systems are designed and manufactured for reliable operation when placed 2 meters from the source of the noise.
  • Page 60 Environmental specifications State Condition Hitachi does not test storage systems and data drives (includes HDDs, SSDs, and FMDs) for compatibility with fire suppression systems and pneumatic sirens. Hitachi also does not provide recommendations or claim compatibility with any fire suppression systems and pneumatic sirens.
  • Page 61: Shared Memory

    9.8m/s (1.0G) equivalent to NEBS (Network Equipment-Building System) Level3). Shared memory Using Hitachi software products, the number of pairs, migration plans, and pool capacities and virtual volumes depend on the amount of capacity of shared memory installed on the controller.
  • Page 62 Table 23 Minimum cache memory capacity required for shared memory function Shared Memory Function VSP F350 VSP F370 Base 64 GiB 128 GiB Extension1 128 GiB 128 GiB Extension2 128 GiB 256 GiB Extension3 Appendix B: System specifications Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 63: Appendix C: Network Access

    Review the following ports before you install the storage system to avoid conflicts between the TCP/IP port assignments used by the storage system and those used by other devices and applications. Appendix C: Network access Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 64 Interface (CCI) data collection procedures. 34001 Used by RAID Manager. 51099 Used by Device Manager - Storage Navigator for communication. 51100 Used by Device Manager - Storage Navigator for communication. Appendix C: Network access Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 65 S is not used. or later Automatic 88-02-0x -xx/00 allocation or later CommonJettySt HTTP 8080 88-02-0x -xx/00 or later CommonJettySt HTTP 8210 RestAPIServerS HTTP 9210 DeviceJettyStart HTTP 8081 Appendix C: Network access Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 66: Controller Connections

    ■ Physical service processor connections The SVP is available as an optional, physical device provided by Hitachi Vantara or as a virtual guest host running on customer-provided ESX servers and VM/OS licenses and media. The SVP provides error detection and reporting and supports diagnostic and maintenance activities involving the storage system.
  • Page 67 SVP Guest OS (1 DKC) Windows 10 IoT Enterprise ■ 2 x vCPU ■ 1 virtual network adapter ■ 4 GB RAM ■ 120 GB disk space ■ Appendix C: Network access Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 68: Appendix D: Data And Power Cables

    Serial-attached SCSI (SAS) cables are used to connect drive trays to controllers and other drive trays. Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 69 Fibre Channel cable length based on cable size and port speed. Cable size Speed Maximum cable length 9 micron 1 Gbps 1 km (3281 ft) 2 Gbps 2 km Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 70: Fibre Channel Cables

    Note: Due to high-speed serial data transfer via Fibre Channel, use high- quality FC cables that comply with the Fibre Channel-PH standard. The following figure shows FC direct connection and FC connection through a switch. Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 71 114.8 ft (35 m) 328.08 ft (100 410.1 ft (125 m) — 32 Gbps 65.62 ft (20 m) 229.7 ft (70 m) 328.08 ft (100 — Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 72 (OMx) 850 nm LC-LC cable DXLC-2PS- 9/125 μm (longwave) SPC-xxM- Singlemode Wavelength: 10/125-2SR 1300 nm The following figure shows the connector used for optical interfaces. Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 73: Iscsi Cables

    Cable One side Other side LC-LC cable Optical Equivalent 50, 125 mm to DXLC-2P- Multimode connector connector PC-xxM- Wavelength: GC50, 850 nm 125-2SR (OMx) Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 74 LC connector type ■ Connector type: LC duplex receptacle connector ■ Interval: 6.25 mm flat type, two rows ■ Cable specifications for 10 Gbps iSCSI copper interface Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 75 10 Gbps 10GBASE-T STP ( use an RJ-45 LAN cable STP cable that suppresses radio noise) The following figure shows a 10 Gbps iSCSI cable. Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 76: Iscsi Standards

    With Linux software port) initiator, the maximum number decreases. Path failover HDLM Supports Microsoft MPIO (Multi Path I/O) Link 10 Gbps SFP+ Transfer speed 10 Gbps Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 77 Port IPv6 is set to Enabled, verify the IPv6 router is connected to the same network, and then set IPv6 global address automatically. Subnet mask Supported Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 78 The storage system follows the host's digest setting. If digest is enabled, the performance degrades. The amount of the degradation depends on Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 79: Managing Cables

    ASCII-coded, hexadecimal, EUI-64 identifier. Example: eui.0123456789abcdef Managing cables Organize cables to protect the integrity of your connections and allow proper airflow around your storage system. Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 80 40 mm (1.73 inch) iSCSI optical 40 mm (1.73 inch) Category 5 Ethernet Four times the outside diameter of the cable 40 mm (1.73 inch) Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 81 Cabling full-width modules When cabling full-width modules, route the cables horizontally, so that they do not interfere when replacing a module. Ensuring adequate airflow Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 82: Ac Power Cables

    ■ AC power cables Utility AC power standards for connector types and voltage levels vary by country. Hitachi provides a variety of power cables that facilitate using storage systems around the world. Hitachi power cables meet the safety standards for the country for which they are intended.
  • Page 83 South Africa 200-240 10, 16 SABS-164 Switzerland 200-240 SEV 1011 International 200-240 IEC 309 United 200-240 BS-1363 Kingdom International 200-240 IEC 309 International 200-240 IEC 309 Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 84: Ac Connections

    3 IEC 83 NEMA L6-20P 200V-240V 1 ANSI C73.11 2 NEMA 6-15P 3 IEC 83 CEE 7/7 200V-240V 4 CEE (7) II, IV, VII 3 IEC 83 Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 85 AC connections Reference Description Receptacle Input rating standards BS-1363 200V-240V 5 BS 1365 3 IEC 83 AS-3112 200V-240V 6 AS C112 Cable and connector Appendix D: Data and power cables Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 86: Power Cable Usage Guidelines

    Power cable usage guidelines Power cable usage guidelines Hitachi storage systems are intended for rack installation and ship with power cords. Installation and service requirements may require additional cords and cables to be ordered. The type of power cable required by a given installation is determined primarily by the: Type of AC line feed provided by the facility.
  • Page 87: Appendix E: Power Distribution Units For Hitachi Universal V2B Rack

    Balance the electrical current load between available PDUs. ■ Americas single-phase PDU 1P30A-8C13-3C19UL.P The following figure and table describe the specifications of the PDU. Figure 1 Americas PDU for the Hitachi Universal V2B Rack (Single-phase PDU 1P30A-8C13-3C19UL.P) Power Total rack...
  • Page 88: Americas Single-Phase Pdu 1P30A-15C13-3C19Ul.p

    4.5 m (14.76 feet) cable Americas single-phase PDU 1P30A-15C13-3C19UL.P The following figure and table describe the specifications of the PDU. Figure 2 Americas PDU for the Hitachi Universal V2B Rack (Single-phase PDU 1P30A-15C13-3C19UL.P) Power Total rack Part Power input...
  • Page 89: Americas Three-Phase Pdu 3P30A-8C13-3C19Ul.p

    Americas three-phase PDU 3P30A-8C13-3C19UL.P Americas three-phase PDU 3P30A-8C13-3C19UL.P The following figure and table describe the specifications of the PDU. Figure 3 Americas PDU for the Hitachi Universal V2B Rack (Three-phase PDU 3P30A-8C13-3C19UL.P) Power Total rack Part Power input output per...
  • Page 90: Americas Three-Phase Pdu 3P30A-24C13-6C19Ul.p

    Americas three-phase PDU 3P30A-24C13-6C19UL.P Figure 4 Americas PDU for the Hitachi Universal V2B Rack (Three-phase PDU 3P30A-15C13-3C19UL.P) Power Total rack Part Power input output per amperage number Region Quantity per PDU available 3P30A-15C Americas 4/rack Three phase 15 IEC C13 77A (16kVA) 13-3C19UL.
  • Page 91: Apac And Emea Single-Phase Pdu 1P32A-9C13-3C19Ce.p

    APAC and EMEA single-phase PDU 1P32A-9C13-3C19CE.P Figure 5 Americas PDU for the Hitachi Universal V2B Rack (Three-phase PDU 3P30A-24C13-6C19UL.P) Power Total rack Part Power input output per amperage number Region Quantity per PDU available 3P30A-24C Americas 2/rack Three phase 24 IEC C13 38.4A (8kVA)
  • Page 92: Apac And Emea Single-Phase Pdu 1P32A-18C13-3C19Ce.p

    APAC and EMEA single-phase PDU 1P32A-18C13-3C19CE.P Figure 6 APAC and EMEA PDU for the Hitachi Universal V2B Rack (Single-phase 1P32A-9C13-3C19CE.P) Power Total rack Part Power input output per amperage number Region Quantity per PDU available 1P32A-9C1 APAC and 6/rack Single phase 9 IEC C13 + 77A (17.6kVA)
  • Page 93: Apac And Emea Three-Phase Pdu 3P16A-9C13-3C19Ce.p

    APAC and EMEA three-phase PDU 3P16A-9C13-3C19CE.P Figure 7 APAC and EMEA PDU for the Hitachi Universal V2B Rack (Single-phase 1P32A-18C13-3C19CE.P) Power Total rack Part Power input output per amperage number Region Quantity per PDU available 1P32A-18C APAC and 4/rack Single phase 18 IEC C13 77A (17.6kVA)
  • Page 94: Apac And Emea Three-Phase Pdu 3P16A-15C13-3C19Ce.p

    APAC and EMEA three-phase PDU 3P16A-15C13-3C19CE.P Figure 8 APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase 3P16A-9C13-3C19CE.P) Power Total rack Part Power input output per amperage number Region Quantity per PDU available 3P16A-9C1 APAC and 6/rack Three phase 9 IEC C13 + 115A (26.4kVA)
  • Page 95: Apac And Emea Three-Phase Pdu 3P32A-24C13-6C19Ce.p

    APAC and EMEA three-phase PDU 3P32A-24C13-6C19CE.P Figure 9 APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase 3P16A-15C13-3C19CE.P) Power Total rack Part Power input output per amperage number Region Quantity per PDU available 3P16A-15C APAC and 4/rack Three phase 15 IEC C13 77A (17.6kVA)
  • Page 96: Americas, Apac, And Emea Three-Phase Pdu 3P30A-243-69Ce-Ul.p

    Americas, APAC, and EMEA three-phase PDU 3P30A-243-69CE-UL.P Figure 10 APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase 3P32A-24C13-6C19CE.P) Power Total rack Part Power input output per amperage number Region Quantity per PDU available 3P32A-24C APAC and 2/rack...
  • Page 97 Americas, APAC, and EMEA three-phase PDU 3P30A-243-69CE-UL.P Figure 11 APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase 3P30A-243-69CE-UL.P) Power Total rack Part Power input output per amperage number Region Quantity per PDU available 3P30A-243- Americas, 2/rack Three phase 24 IEC C13 77A (17.6kVA)
  • Page 98: Appendix F: Non-Hitachi Racks

    PDUs and cable loops. Hitachi Universal V2 Rack rail kits Use rail kits to mount the Hitachi Virtual Storage Platform family storage system in a Hitachi Universal V2 Rack. The following tables list the rail kit information for the specified storage systems.
  • Page 99: Hitachi Universal V2 Rack Accessories

    Optional, must be Included with rack Not included with rack, must be ordered ordered separately separately. A quantity of two must be (A3BF-DR). ordered per rack (A3BF-Z-PAN-1200). Appendix F: Non-Hitachi racks Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 100: Appendix G: Warning Labels On The Storage System

    Use caution when handling equipment with movable parts. Use caution when handling equipment with hot surfaces. Use caution when handling equipment prone to tipping over. Appendix G: Warning labels on the storage system Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 101: Cbss Controller

    CBSS controller CBSS controller Appendix G: Warning labels on the storage system Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 102: Cbsl Controller

    CBSL controller CBSL controller Appendix G: Warning labels on the storage system Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 103: Small Form Factor Drive Tray

    Small form factor drive tray Small form factor drive tray CBSS/CBSL controller Appendix G: Warning labels on the storage system Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 104: Battery

    Battery Battery Appendix G: Warning labels on the storage system Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 105: Appendix H: Environmental Notices

    They will dispose of it for you. This nickel-metal hydride battery, which is designated as recycling product by a recycling promotion low, must be recycled. The mark posted on the Cache Backup Battery is a three-arrow mark that indicates a recyclable part. Appendix H: Environmental notices Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 106: Appendix I: Regulatory Compliance

    Appendix I: Regulatory compliance This equipment has been tested and certified for compliance with the following standards. Appendix I: Regulatory compliance Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 107 All CB countries 1+A2 IEC60950-1:2005+A S_Mark Argentina 1+A2 TP TC 004/2011 Russia CNS 14336-1 BSMI Taiwan EN60950-1:2006+A1 CE marking 1+A1+A12+A2 Radio interference VCCI V-3/2015.4 VCCI Japan voluntary control Appendix I: Regulatory compliance Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 108 This is a class A product. In a domestic environment this product can cause radio interference in which case the user can be required to take adequate measures. Appendix I: Regulatory compliance Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide...
  • Page 109 Hitachi Vantara Corporate Headquarters Contact Information 2535 Augustine Drive USA: 1-800-446-0744 Santa Clara, CA 95054 USA Global: 1-858-547-4526 HitachiVantara.com | community.HitachiVantara.com HitachiVantara.com/contact...