Parameter assignment
6.4 Setting the commissioning parameters
Parameter
Load cell characteristic value
(Page 24)
Zero point offset
Modbus address
For SG-Shield OEM
Set the RS485 Modbus ad‐
dress using the DIP switch.
Check the RS485 Modbus ad‐
dress during commissioning.
Reserve
Baud rate
0: 9600 bps
1: 19200 bps
2: 38400 bps
3: 57600 bps
4: 115200 bps
Character parity
0: Even
1: Odd
2: No parity
Number of data bits
0: 7 data bits
1: 8 data bits
Number of stop bits (only for SG-
Shield OEM)
0: 1 stop bit
1: 2 stop bits
Byte swap for text fields (only for
SG-Shield OEM)
0: No byte swap
1: Byte swap
Byte swap for 16-bit values (only
for SG-Shield OEM)
0: Big endian (MSB first)
1: Little endian (LSB first)
Byte swap for 32-bit values (only
for SG-Shield OEM)
0: Big endian (MSB first)
1: Little endian (LSB first)
20
Format
Length
[bytes]
float
4
float
4
unsigned16
2
unsigned16
2
unsigned16
2
unsigned16
2
unsigned16
2
unsigned16
2
unsigned16
2
unsigned16
2
unsigned16
2
r/w
Default
r/w
4.00000
r/w
0.0
r
SG-
Shield OEM: 0
SIMATIC
IOT2000 SG-
Shield: 246
r/w
0
r/w
SG-
Shield OEM: 1
SIMAT‐
IC IOT2000 SG
-Shield: 4
r/w
0
r/w
1
r/w
0
r/w
1
r/w
0
r/w
0
Operating Instructions, 08/2021, A5E50985404-AA
Min
Max
Mod‐
bus ad‐
dress
-4.8
+4.8
1113
-20000.0 +20000.0 1121
-
-
4000
0
127
4001
0
4
4002
0
2
4003
0
1
4004
0
1
4005
0
1
4006
0
1
4007
0
1
4008
SIMATIC IOT2000 SG-Shield