To increase the safety level when EDM is OFF when the light curtain is commissioned,
ensure that the EDM input is not connected.

7.6 Reduced range

This function enables you to select the maximum operating range for the light curtain's
assembly.
The table below summarises the different operating ranges, if the reduced operating range is
changed.
Resolution 30 mm
long range
short range
Long
Reduced
If long range is selected, the TX and RX can be installed at the maximum permitted operating
range.

7.7 Muting

The muting function guarantees that the safety function is automatically disabled over all or
part of the height of the detection zone, to enable specific, cyclical work operations to be
carried out without having to stop the machine operation.
In accordance with safety requirements, the light curtain is equipped with two inputs for
activating the muting function, MUTING1 and MUTING2.
The muting sensors must be able to detect the conveyed material (pallets, vehicles,...)
based on their length and speed. Where there are variable conveyor speeds within the
muting area, you must consider the effect this will have on the overall duration of the muting
process.
• The muting function excludes the light curtain during operation and maintains the
OSSD output switching elements in an activated state, based on the specific operating
requirements (Fig. 39).
40
Fig. 38 – Reduced range
BCM configuration (TX-side): Reduced range
LED 3 ON yellow
LED 3 OFF
TX
20 m
12 m
PSEN op2H-A series
LEVEL
1003069-EN-03