Lev, Thermistor (Liquid/Gas Piping Temperature Detection) - Mitsubishi Electric CITY MULTI PEFY Series Technical And Service Manual

Ceiling concealed (fresh air intake type)
Hide thumbs Also See for CITY MULTI PEFY Series:
Table of Contents

Advertisement

[ VIII Disassembly Procedure ]

3. LEV, thermistor (Liquid/Gas piping temperature detection)

Be careful on removing heavy parts.
1. Removing the LEV.
(1) Remove the control box cover with procedure [2]-1.
(2) Remove the fixing screws (three) of the heat exchanger
cover (A), and remove the cover (A). (Fig.1)
(3) Remove the LEV driving motor. (Fig.2)
2. Removing the liquid pipe and gas pipe thermistor.
(1) Remove the thermistors from the thermistor holders
which are installed on the piping. (Fig.3)
3. Removing the outlet air temperature thermistor.
(1) Remove control box cover with procedure [2]-1.
(2) Remove the fixing screws (three) of the heat exchanger
cover (A), and remove the cover (A). (Fig.1)
(3) Remove the fixing screws (four) of maintenance cover
(B), and remove the cover (B). (Fig.1)
(4) Remove the cable bush from the panel, and pull the outlet
air temperature thermistor through the hole. (Fig.4)
HWE1804A
(A)
Fig.1
LEV
Fig.2
P72
Thermistor
Fig.3
Fig.4
- 35 -
(B)
P96
Thermistor
Cable bush
GB