[ VII Troubleshooting ]
VII Troubleshooting
[1] Troubleshooting
1. Check methods
1. Component and check points
(1) Thermistor
Inlet air temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Outdoor air temperature thermistor (TH24)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C)
Normal
4.3kΩ - 9.6kΩ
(Refer to the thermistor characteristic graph below.)
1) Thermistor characteristic graph
Thermistor R
= 15 kΩ 3%
0
Multiplier of B = 3480 kΩ 2%
Rt = 15 exp { 3480(
273+t
0°C 15kΩ
10°C 9.6kΩ
20°C 6.3kΩ
25°C 5.2kΩ
30°C 4.3kΩ
40°C 3.0kΩ
(2) Fan motor (CNMF)
Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
CN60
(F)
1
(E)
2
(D)
3
M
(C)
4
LEV
(A)
6
(A)
Red
(C)
Blue
(D)
Orange
HWE1804A
Abnormal
Open or short
50
1
1
) }
273
40
30
20
10
Normal
1-6
2-6
White-Red
Yellow-Red
(150Ω)
(E)
Yellow
(F)
White
0
-20
-10
0
10
20
30
Temperature(°C)
3-6
4-6
Orange-Red
Blue-Red
10%
- 14 -
40
50
Abnormal
Open or short
GB