Installation procedure

Pipe specification
Liquid pipe
E
Gas
Gas pipe
Liquid pipe
pipe
E
1. Pipe "A" diameter (between indoor and branch pipe) (depends on indoor pipe)
Indoor (x100W)
18~28
32~56
63~160
226-300
450-600
Note:
• If the distance between the unit and the nearest branch ≥ 15m, Pipe "A" should be enlarged:
(1) The capacity of indoor unites ≤ 5.6kW, the gas pipe change to Ø15.88, the liquid pipe change to Ø9.52.
(2) 5.6kW ˂ the capacity of indoor unites ˂ 16.8kW,the gas pipe change to Ø19.05, the liquid pipe change to Ø9.52.
(3) The capacity of indoor unites ≥ 16.8kw,the liquid pipe change to Ø12.7.
• The first sub-manifold distance from the longest indoor unit piping length ≥ 40 meters:
(1) The first sub-manifold to the nearest indoor unit main pipe (gas /liquid pipe) must increase a specification.
(2) The distance between the nearest indoor unit distance between the indoor unit ≤ 40 meters.
2. Pipe "B" diameter (between branch pipes)
Total indoor capacity after the branch pipe (kW)
˂14kW
14kW≤ X ˂16.8kW
16.8kW≤ X ˂28.0kW
28.0kW≤ X ˂33.5kW
33.5kW≤ X ˂45.0kW
45.0kW≤ X ˂71.0kW
71.0kW≤ X ˂101.0kW
101.0kW≤ X ˂158.0kW
158.0kW≤ X ˂186.0kW
186.0kW≤ X ˂240.0kW
240.0kW≤ X ˂275.0kW
≥275kW
Outdoor
Gas pipe
Liquid pipe
Gas pipe
D
D
D
D
outdoor gather pipe
Gas pipe
Liquid pipe
Ø9.52
Ø6.35
Ø12.7
Ø6.35
Ø15.88
Ø9.52
Ø25.4
Ø9.52
Ø28.58
Ø12.7
Liquid pipe
C
C
the first branch pipe
Note:
AS072 AS092 gas pipe: Ø12.7, AS182 gas pipe/ liquid pipe:
Ø15.88/9.52.
Gas pipe
According to the pipe A pipe diameter
Ø15.88
Ø19.05
Ø22.22
Ø28.58
Ø28.58
Ø31.8
Ø38.1
Ø41.3
Ø44.5
Ø50.8
Ø54.1
14
Indoor
A
A
A
A
B
B
B
B
Liquid pipe
Ø9.52
Ø9.52
Ø9.52
Ø12.7
Ø15.88
Ø19.05
Ø19.05
Ø19.05
Ø22.22
Ø25.4
Ø25.4