Haier AV08IMVEVA Installation Manual page 6

Advertisement

Installation instruction
Capacity
HP
Combination Type
(W)
58
162400
combination(18+20+20)
60
168000
combination(20+20+20)
62
173500
combination(20+20+22)
64
179000
combination(20+22+22)
66
184500
combination(22+22+22)
68
191000
combination(22+22+24)
70
197500
combination(22+24+24)
72
204000
combination(24+24+24)
74
209500
combination(24+24+26)
76
215000
combination(24+26+26)
78
220500
combination(26+26+26)
80
224000
combination(20+20+20+20)
82
229500
combination(20+20+20+22)
84
235000
combination(20+20+22+22)
86
240500
combination(20+22+22+22)
88
246000
combination(22+22+22+22)
90
252500
combination(22+22+22+24)
92
259000
combination(22+22+24+24)
94
265500
combination(22+24+24+24)
96
272000
combination(24+24+24+24)
98
277500
combination(24+24+24+26)
100 283000
combination(24+24+26+26)
102 288500
combination(24+26+26+26)
104 294000
combination(26+26+26+26)
Note:
a. If all the indoor units operate at the same time in one system, the total indoor units capacity should be less than or
equal to the total outdoor units capacity. Otherwise,overloading operations may occur in bad operating condition or
some special conditions. If all the indoor units don't operate at the same time in one system,the total indoor units
capacity should be no more than 130% of the total outdoor units capacity.
c. If the system operates in high heat load or cold area (Ambient Temperature below -10°C), the total indoor units capacity
should be less than the total outdoor units capacity.
d. To choose combinations' wires and air switches according to the Max. operating current of the combinations.
Installation place selection
Air-conditioner can't be installed in the
place with inflammable gas. Or it will
cause fire hazard.
The most
Allow the most
recommended
connected
indoor unit
indoor units
96
99
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
The unit should be installed at the
place with good ventilation. No
obstacle at the air inlet/outlet. And no
strong wind blows the unit.
The installation space refers to the
latter info.
4
Indoor
Total indoor
capacity(100W)
number
61
812~2111
63
840~2184
64
868~2256
64
895~2327
64
922~2398
70
955~2483
70
988~2568
70
1020~2652
70
1048~2723
70
1075~2795
76
1103~2867
76
1120~2912
76
1148~2984
76
1175~3055
76
1203~3127
76
1230~3198
85
1263~3283
85
1295~3367
85
1328~3452
85
1360~3536
85
1388~3608
85
1415~3679
89
1443~3751
89
1470~3822
The unit should be installed at the
strong enough place. Or it will cause
vibration and noise.
Combined
Gather pipe
capacity
range
HZG-30B
50%~130%
HZG-20B
HZG-30B