Installation Manual for Commercial Air Conditioner
Outdoor Unit
No. 0150530707
• Please read this manual carefully before using.
• Keep this operation manual for future reference.
Original instructions
AV08IMVURA
AV10IMVURA
AV12IMVURA
AV14IMVURA
AV16IMVURA
AV18IMVURA
AV20IMVURA
AV22IMVURA

Advertisement

loading

Summary of Contents for Haier AV08IMVURA

  • Page 1 Installation Manual for Commercial Air Conditioner Outdoor Unit AV08IMVURA AV10IMVURA AV12IMVURA AV14IMVURA AV16IMVURA AV18IMVURA AV20IMVURA AV22IMVURA No. 0150530707 • Please read this manual carefully before using. • Keep this operation manual for future reference. Original instructions...
  • Page 2: Table Of Contents

    User Manual Contents Safety ....................................1 Installation instruction ................................3 Installation procedure ..............................13 Electric wiring and the application ...........................27 Failure code ..................................40 Trial operation and the performance ..........................45 Move and scrap the air conditioning ..........................46 Operation condition: Operating Range of Air Conditioner To use the air conditioner normally, please perform as to the Max.
  • Page 3: Safety

    Safety • If the air conditioner is transferred to the others, this manual should be tranferred together. • Before installation, please read "Safety precaution" carefully to confirm the correct installation. • The mentioned precaustion includes " WARNING" and " CAUTION". The precausion caused death or heavy injury for faulty installation will be listed in "...
  • Page 4 Safety CAUTION • Execute earthing for the unit. But the earthing wire can not be connected to the gas pipe, water pipe, lightening rod or the telephone earthing wire. Improper earthing will cause electric shock. • Don't install the unit at the place where leaks the flammable gas. Or it will cause fire. •...
  • Page 5: Installation Instruction

    Installation instruction In installation, please check specially the below items: • If the connected units quantity and the total capacity is in the allowable range? • If the refrigerant pipe length is in the limited range? • If the pipe size is proper? And if the pipe is installed horizontally? •...
  • Page 6 Installation instruction Outdoor Indoor Capacity (100W) Combination type Indoor Qty Total indoor capacity (kBtu/h) Gather pipe 1908 Combination (450+450+504+504) 1~64 960~2496 1962 Combination (450+504+504+504) 1~64 988~2568 2016 Combination (504+504+504+504) 1~64 1020~2652 2072 Combination (504+504+504+560) 1~64 1048~2723 2128 Combination (504+504+560+560) 1~64 1075~2795 2184 Combination (504+560+560+560)
  • Page 7 Installation instruction Transportation • In transportation, please don't dismantle the packaging, and move the unit to the installation location as closely as possible. • Don't hang the unit only at two points. When hanging the unit, don't sit on the unit. The unit should be upright. When removing the unit with the forklift, put the fork into the special hole at bottom of the unit.
  • Page 8 Installation instruction Outline and installation dimensions Fixed hole distance AV08~14IMVURA 800mm Drain hole 750mm 980mm 70mm Exhaust duct connection position Power line outlet (According to the choice of the power line diameter size. The export, use the attached wire into the sheath) Signal line and Line protection Signal wire hole diameter Ø25...
  • Page 9 Installation instruction Outdoor unit installation Standard accessories Please check the attachment is complete, please be sure to use. No. definition Graphic Quantity Remarks Place position Installation Accessory bag instruction Rubber Signal line Accessory bag plug protection Power line sheath Accessory bag protection (8HP) (10HP)
  • Page 10 Installation instruction Combination installation dimensions • There should be no obstacles in 2000mm above the top of outdoor unit; • Obstacles around outdoor should be greater than 900mm to the bottom of unit. • When multiple modules are installed, the outdoor should be in ranked as the capacity, the larger capacity is closer to the main pipe of gather pipe.
  • Page 11 Installation instruction ˃300mm ˃200mm ˃300mm ˃1000mm 3. Wall higher than the outdoor condenser Place with air inlet hole Notes: a. Fan speed Vs at air inlet is 1.5m/s or below. b. Air outlet height HD=H-h and below 1m. ˃300mm ˃200mm ˃1000mm ˃300mm External air...
  • Page 12 Installation instruction Place without air inlet hole Notes: a. Set a 500~1000mm bracket. b. Air outlet height HD=H-h and below 1m. ˃300mm ˃300mm ˃200mm ˃1000mm External air duct 4. The outdoor machine installation should consider the impact of seasonal wind, don't let the wind directly into the unit return air, otherwise it will affect the unit defrosting and related functions 5.
  • Page 13 Installation instruction install snow cover Outlet snow cover Snowfall area, please install snow cover, see the right Inlet snow cover picture,To be unaffected by the snow, it is important to set up a high platform, which is calculated according to the maximum amount of snow in the area.
  • Page 14 Installation instruction Install air ducting There are no obstacles in the 2000mm above the outdoor unit; When there are obstacles in the outer plane, there must be a pilot channel, and the wind will be free, the wind will not beshort-circuited, and the external static pressure will be less than 110Pa.
  • Page 15: Installation Procedure

    19.05 is O-type, the pressure preservation will be bad, thus it must be 1/2H type and over the min. thickness. 3. The branch pipe and the gather pipe must be from Haier. 4. When installing the stop valve, refer to the relative operation instruction.
  • Page 16 Installation procedure Pipe specification Outdoor gather pipe The first branch pipe a a a 1. Pipe "a" diameter (between indoor and branch pipe) (depends on indoor pipe) Indoor (x100W) Gas pipe(mm) Liquid pipe(mm) 22~28 Ø9.52 Ø6.35 36~56 Ø12.7 Ø6.35 71~140 Ø15.88 Ø9.52 226~300...
  • Page 17 Installation procedure 3. Pipe "c" diameter (between VP and branch pipe) (depends on VP pipe) Suction gas pipe (mm) HP gas pipe (mm) Liquid pipe (mm) 112B Ø15.88 Ø12.7 Ø9.52 180B Ø15.88 Ø15.88 Ø9.52 280B Ø22.22 Ø19.05 Ø9.52 4. Pipe "d" diameter (between VP branch pipes) Total indoor capacity after the branch pipe Suction gas pipe HP gas pipe...
  • Page 18 Installation procedure Main pipe Enlarged main pipe Outdoor Outdoor Suction gas HP gas Liquid Suction gas HP gas Liquid capacity (HP) capacity (kW) pipe(mm) pipe(mm) pipe(mm) pipe(mm) pipe(mm) pipe(mm) 173.5 Ø41.30 Ø38.10 Ø19.05 Ø44.50 Ø41.30 Ø22.22 179.0 Ø41.30 Ø38.10 Ø19.05 Ø44.50 Ø41.30 Ø22.22...
  • Page 19 Installation procedure Long pipe and high drop 1. Allowable piping length and drop between indoor and outdoor Outdoor 3 Outdoor is only one L12 L13 Outdoor 1 The outdoor is more than one unit When the distance between outdoors(L1, L3) is over 2m, the oil trap must be set (upright projecting pipe, 200mm high), as the figure : Outdoor 2 Outdoor 3...
  • Page 20 Installation procedure 2. Applicable range Item Model All outdoors Pipe in above figure Single way total pipe length 1000 m (correspond length) L1+L2+L3……+L22 Single way pipe length Max. 165/190 (correspond length) L1+L3+ L5+L6+L7+L8+L9+L10 Main pipe beween outdoor to 1st branch Max.130 (correspond length) Height difference between Outdoor is upper...
  • Page 21 Installation procedure Proper installation Wrong installation Oil return bend Compressor oil will flow into The height of the vertical the lowest unit section see schedule requirements In order to avoid damage to the pipe, the size of the return bend is referred to as the drawing. Pipe diameter Bending radius Vertical heigh...
  • Page 22 Installation procedure 4. Example of connection Outdoor unit side (3 pipes) HP gas Pipe (Ø12.7) Indoor unit side (2 pipes) Suction gas Pipe (Ø15.88) 112B Liquid Pipe (Ø9.52) Gas Pipe (Ø15.88) Liquid Pipe (Ø9.52) Outdoor unit side (3 pipes) HP gas Pipe (Ø15.88) Indoor unit side (2 pipes) Suction gas Pipe (Ø15.88) 180B...
  • Page 23 A. Outdoor unit HP gas pip Suction gas pip Liquid pipe Model Diameter Connection Diameter Connection Diameter Connection (mm) method (mm) method (mm) method AV08IMVURA Ø19.05 Ø19.05 Flared Ø9.52 Flared AV10IMVURA Ø19.05 Ø22.22 Ø9.52 AV12IMVURA Ø22.22 Ø25.4 Ø12.7 AV14IMVURA Ø22.22 Ø25.4 Ø12.7...
  • Page 24 Installation procedure B. Indoor unit C. Pipe spec and the torque Torque(N . m) Diameter (mm) Gas pipe side Liquid pipe side Model Diameter Connecting Diameter Connecting Ø6.35 16~20 (mm) method (mm) method Ø9.52 40~50 Ø9.52 Ø6.35 Ø12.7 40~50 Ø9.52 Ø6.35 Ø15.88 90~120...
  • Page 25 Installation procedure Pipe installation Important • Please don't let the pipe and the parts in the unit collide each other. • When connecting the pipes, close the valves fully. • Protect the pipe end against the water, impurity into the pipes (welding after being flat, or being sealed with adhesive tape).
  • Page 26 Installation procedure B. Leakage test 1. The outdoor unit has been executed the leakage test in the factory. The pipe should be executed leakage test individually and forbidden to test after connecting with stop valve. 2. Refer to the below figure to charge the nitrogen into the unit to take a test. Never use the chlorin, oxygen, flammable gas in the leakage test.
  • Page 27 Installation procedure D. Check valve operation Open/ close method: (The suction gas pipe stop valve for AV08IMVURA, AV10IMVURA, AV12IMVURA,AV14IMVURA,AV 16IMVURA,AV18IMVURA,AV20IMVURA,AV22IMVURA) • Take down the valve cap, suction gas pipe, HP gas pipe turns to "open" • Turn the liquid pipe and the oil equalization pipe with hexangular spanner until it stops. If opening the valve strongly, the valve will be damaged.
  • Page 28 Installation procedure Note: • To prevent the oil going into the pipe, please use the special tool for R410A, especially for gauge manifold and charging hose. • Mark the refrigerant type in different colour on the tank. R410A is pink. •...
  • Page 29: Electric Wiring And The Application

    Power Circuit Each module Model load current (mA) sectional area of area of earthing source breaker circuit breaker response time(S) power line (mm line (mm AV08IMVURA 20.3 AV10IMVURA 21.8 AV12IMVURA 23.3 3N~, AV14IMVURA 27.7 30mA, below0.1s 380-415V, AV16IMVURA 32.4 50/60Hz AV18IMVURA 36.1...
  • Page 30 Electric wiring and the application 2. If the power cord length is greater than 20m, please increase the cable cross-sectional area, so as to avoid overload caused by the accident. 3. When the voltage drop at the power supply line exceeds 2%, increase the wire diameter appropriately. 4.
  • Page 31 Electric wiring and the application Power line installation instructions Note: When connecting the power cord, please be sure to set aside enough length in the outdoor, which is convenient for turning over the electrical box. After the maintenance, remove the 5 fixing screws, the electric appliance box body is lifted up slightly, and the box body is rotated to the left, and the steel wire rope in the column is used to check the box to prevent the turning.
  • Page 32 Electric wiring and the application Communication wiring figure (Wired) control wire for wired controller with polarity Communication wire with polarity Note: • Outdoor units are in parallel through 3 polar wires. The outdoor and all VP (cooling and heating switching device) and all indoor units are in parallel through 2 non-polar wires.
  • Page 33 Electric wiring and the application B. One wired controller controls one indoor unit, as shown in the above figure (indoor unit 6-19). The indoor unit and the wired controller are connected via three lines with polarity. C. Two wired controllers control one indoor unit, as shown in the figure (indoor unit 20). Either of the wired controllers can be set to be the master wired control while the other is set to be the slave wired controller.
  • Page 34 Electric wiring and the application 2. Follow the instructions to route. IGU09 Connecting line 3. Make the dial setting - see the setting method. 4. Installation notes - see the IGU09 installation instructions. Internal layout of electric appliance box For example Compressor drive module...
  • Page 35 Electric wiring and the application Outdoor dip switch introduction Identification: • Physical master unit: by setting dip switch, the unit number is 0. It is used to communicate with indoor unit, also it is the organizer of outdoor communications as communication master unit. •...
  • Page 36 Electric wiring and the application ③ BM3 introduction BM3_1 BM3_2 BM3_3 Outdoor Normal BM3_1 The outdoor Outdoor machine model Update use BM3_2 machine is Enhanced vapor injection BM3_3 effective model Three pipe model BM3_5 BM3_6 BM3_7 BM3_8 Outdoor horse BM3_5 10HP BM3_6 12HP...
  • Page 37 Electric wiring and the application Outdoor machine digital tube display settings The contents of the display are defined as follows: • Key parts: long press the left START (SW5) control to enter, short press above UP (SW4) data increase, short press down DOWN (SW7) data reduction, long press the right STOP (SW6) control exit •...
  • Page 38 Electric wiring and the application function Digital tube LD1 ~ 4 display (1) press START (SW5) for 2 seconds, to enter the instruction set state, flashing display instructions. Forced indoor mechanism (2) according to UP (SW4) or DOWN (SW7) () adjustment instructions (COOL/ 14(E)...
  • Page 39 Electric wiring and the application function Digital tube LD1 ~ 4 display Outdoor unit LEVa1 open degree 0---470pluse Press START (SW5) for 2 seconds, 1111, enter the Outdoor unit LEVa2 open degree set state: flashing, press UP (SW4) valve fully open, according to DOWN (SW7) 2min after the valve is fully Outdoor unit LEVb open degree closed;...
  • Page 40 Electric wiring and the application function Digital tube LD1 ~ 4 display Outdoor 14(E) 15(F) Frequency converter INV1 module temperature Unit: degree unit address 15(F) 15(F) Frequency converter INV2 module temperature Unit: degree ③ System status display and control (host) function Digital tube LD1 ~ 4 display Refrigerant type...
  • Page 41 Electric wiring and the application Control function Digital tube LD1 ~ 4 display range 0- machine automatic control according to the In the same machine drive group number, all within the machine with 15(F) off control selection 1- drive, 2- all in each machine control, drive off with ban Selection of low temperature 0- within the machine automatic control, 15(F)...
  • Page 42: Failure Code

    Failure code Failure code description: (failure code of the whole system is showed as 8 bits, so totally 256 codes. Indoor failure code should be judged by the table and the unit number) • Outdoor failure code exists in EEPROM, in which 5 failure codes can be kept. •...
  • Page 43 Failure code Digital tube indication Failure code definition Failure description Remarks on master unit The searched vp box quantity is less than set quantity for 26-3 continuous 5 minutes Outdoor unit and VP-box communication failure The searched vp box quantity is more than set quantity for 26-4 continuous 5 minutes Oil temp.too high...
  • Page 44 Failure code Digital tube indication Failure code definition Failure description Remarks on master unit After compressor is running,compression ratio ε > 10.0 Compression ratio too Once forcontinuous 5 minutes ,stop and alarm。2 minutess and 50 39-1 high confirmation Seconds later,resume automatically。If it occurs 4 times in an Protection un-resumable hour,confirm the failure。...
  • Page 45 Failure code Digital tube indication Failure code definition Failure description Remarks on master unit Module rectifier side software transient overcurrent Module rectifier side current detection circuit anomaly Module hardware overcurrent In the process of starting or running, the rotor position can not Compressor out of step be detected for 6 times in a row, and the INV control board is automatically restored after stopping 5S...
  • Page 46 Failure code In the case of no fault, if the system does not meet the start-up conditions, the host digital display standby code: Indoor machine capacity beyond the outdoor Indoor machine capacity beyond the outdoor 555.0 machine capacity of 150% or less than 50%, machine capacity of 150% or less than 50%, standby standby system system...
  • Page 47: Trial Operation And The Performance

    Trial operation and the performance 5-minute delay function • If starting up the unit after being powered off, the compressor will run about 5 minutes later against being damaged. Cooling/heating operation • Indoor units can be controlled individually, but cannot run in cool and heat mode at the same time. If the cool mode and the heat mode are existing simultaneously, the unit set latter will be standby, and the unit set earlier will run normally.
  • Page 48: Move And Scrap The Air Conditioning

    Trial operation and the performance Trial operation • Before trial operation: Before being electrified, measure the resistor between power terminal block (live wire and neutral wire) and the earthed point with a multimeter, and check if it is over 1MΩ. If not, the unit can not operate. To protect compressor, electrify the outdoor unit for at least 12 hours before the unit runs.If the crankcase heater is not electrified for 6 hours, the compressor will not work.
  • Page 52 Qingdao Haier Air Conditioner Electric Co.,Ltd. Haier Industrial Park,Qianwangang Road,Eco-Tech Development Zone,Qingdao 266555, Shandong,P.R.C.