Sensor Position; Straight Pipe Sections - Tecfluid FLOMAT FX FlomatFX Instruction Manual

Electromagnetic insertion sensor
Table of Contents

Advertisement

3.1

Sensor position

The most adequate position is in the side of the pipe. In this way, deposits of particles on
the electrodes and air pockets at the top of the pipe are avoided.
3.2

Straight pipe sections

The point where the Flomat will be installed must be a straight pipe section, separated
from elements that can disturb the flow profile, such as elbows, diameter changes, etc.
Depending on the element the minimum necessary distances upstream from the sensor
must be (BS 1042-2.2:1983 standard):
Type of disturbance upstream from the
sensor
90° elbow or T-bend
Several 90° coplanar bends
Several 90° non-coplanar bends
Total angle convergent 18 to 36°
Total angle divergent 14 to 28°
Fully opened Butterfly valve
Fully opened plug valve
Downstream from the sensor, the minimum recommended distance from a disturbing
element is 5 x DN.
4
60º
60º
Minimum distance between
the sensor and the element
50 x DN
50 x DN
80 x DN
30 x DN
55 x DN
45 x DN
30 x DN