Page 2
Magnetek L1000A Drive EQUIPMENT/SETTINGS VERIFICATION Verify that the Job Specification parameter table on the drawings “Sheet 1: Getting Started” matches the actual equipment. Below is a sample table showing the important values that will affect operation. Motor Motor Motor Volts...
Page 3
CONTROLLER GROUNDING REQUIREMENTS NOTE – For the controller to function properly it is very important to provide proper building ground connections to the controller. Examples of a proper building-to-controller ground connection is to attach the ground cable to: The street side of the incoming water main. ...
Page 4
WIRING – (Check off box when complete) ** Refer to the Appendix for the following connections ** Power – (Sheet 3: Machine Room connections) Connect main line power to terminal block L1/L2/L3. Connect the ground wire to the yellow/green terminal block next to L1-L3.
Page 5
CONSTRUCTION – (Sheet 1: Construction) The following instructions are from the job drawings: “Sheet 1 – Construction”. Refer to the job’s specific drawings for connections. Construction Box (Sample) 24VDC connections to SRU board IOs 120VAC connections to DIN Rail terminals Emergency brake power 24v DC connections...
(Check off box when complete) Apply external power by closing the main disconnect. Close the L1/L2 breaker, the M24, PS, BR and EBR breakers. Verify that the LCD on the Smartrise board and the Magnetek Drive come on. Down = ON...
Page 7
o Use the Up / Down Arrow keys and move the asterix to MISC and press the enter key. SETUP Local Outputs Security *Misc o BYPASS TERM LIMITS should be the first item listed. If it’s not there use the Up / Down Arrow keys and move the asterix to BYPASS TERM LIMITS and press the enter key.
Page 8
The three “Auto Tunes” required are: Motor Tuning, 1 Phase of Encoder Tuning and 2 Phase of Encoder Tuning. ** During the alignment process the Smartrise SRU board will display several faults. These are normal and won’t affect the alignment procedure. ** Stationary Motor Auto-Tuning 1) Install a temporary jumper between H1 on the drive and REF on the DIN rail.
Page 9
INPUTTING MOTOR DATA SAMPLE 1) If the data in the drive doesn’t match the existing equipment, use the following procedures to correct the values: a) Press UP arrow key to access the motor output power parameter T2-04. b) Press ENTER key to view the default setting. c) Press F1 (left), F2 (right), RESET, UP and DOWN arrow keys to enter the motor power nameplate data in kW –...
No Faults Make sure the car is moving without triggering a fault either on the Smartrise SRU or the drive. If the SRU board displays a “Drive Fault” on the SRU, look at the drive to see what the fault is.
WRONG DIRECTION 1. If the car is moving in the wrong direction: a. On the Smartrise controller board make sure that IO 521 comes on when commanding the UP direction and IO 522 comes on when commanding the DOWN direction.
Page 12
APPENDIX Terminal Locations Main Line terminals L1/L2/L3 terminals Terminal / Card location on Motor PG card Brake terminals terminal T1/T2/T3 block Encoder wiring terminals...
Need help?
Do you have a question about the Magnetek L1000A and is the answer not in the manual?
Questions and answers