Huawei UPS5000-S-600 kVA Quick Manual page 9

Three-phase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

2. Set the language, time, date, network parameters, and system parameters on the Settings
Wizard screen.
1. Set system parameters with caution because normal UPS operation depends on correct settings.
Set Single/Parallel with caution. Incorrect setting may affect the normal UPS operation.
Output Voltage level refers to the line voltage level. Set it based on site requirements.
Set Output frequency correctly. Otherwise, the UPS may not work properly and loads may be
affected.
2. Battery parameter settings have great impact on battery maintenance, battery lifespan, and
discharge time.
3. After you perform the settings, the Bypass mode and No battery alarms are reported by the
MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.
4. View the system running status diagram on the MDU to check that the UPS is working in bypass
mode.
9