Huawei UPS5000-S-600 kVA Quick Manual page 10

Three-phase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

5.3
Starting inverter
1. On the main menu, choose Common Functions and tap
Inv. ON.
2. In the displayed login window, enter the user name and
password, and tap
3. In the displayed dialog box, tap Yes to start the inverter.
System User
admin (system administrator)
operator (common user)
Powering On Loads
5.4
1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears.
Check that the UPS has transferred to normal mode by viewing the system running status
diagram. Check that the UPS three-phase output voltage and frequency are normal by viewing
AC Output on the MDU. Use a multimeter to check that the valid three-phase output voltage
and frequency are normal.
2. After confirming that the battery strings are properly connected, close the battery string input
circuit breaker. If there are multiple battery strings, close the circuit breaker for each battery
string and then the general circuit breaker between battery strings and the UPS. The No battery
alarm disappears from the MDU.
3. Close the external output switches to supply power to loads.
(Optional) Setting Parameters for the BCB Box
5.5
(Optional) If a BCB box is configured, choose Settings > Dry Contact Set, set MUE05A
connection to Enable, and then set BCB connection [OL] and Battery breaker [STA] to Enable.
.
LCD Preset Password
000001
000001
To ensure system security,
change the LCD and WebUI
passwords after the first login.
WebUI Preset Password
10
Changeme
Changeme