Enable/Disable Autobaud

Autobaud is disabled by default. You can turn it on or off by following this
procedure.
1. In RSNetWorx for DeviceNet software, click the linking device icon.
2. From the Device pull-down menu, choose Class Instance.
3. If a warning dialog box appears, click Yes.
The Class Instance Editor dialog box appears.
4. From the Description pull-down menu, choose Set Single Attribute.
5. Choose the appropriate options in the Class Instance Editor dialog box.
In This Box
Object Address
Class
Instance
Attribute
Data Sent to Device
Transmit Data Size
IMPORTANT
Rockwell Automation Publication 1788-UM059B-EN-P - September 2015
Choose
3
1
64h
00 to enable Autobaud
01 to disable Autobaud
Byte
Make sure the Values in Decimal checkbox is cleared.
Configure the Linking Device
Chapter 4
49