2.8 User terminal connection

The maximum distance between the μPC and user terminal is shown in the following table.
cable type
telephone
AWG24 shielded cable
Note:
a maximum of one terminal (pGD0, pGD1, pGD-i) can be connected;
the graphic terminal and other terminals are always powered with a separate power supply;
only one terminal (the PLD terminal to connector no. 3 or alternately th-Tune to connector n.ro 4) can be
connected, if the maximum cable-lenght is < 10m;
the protocol supported (RS485 / tLAN protocols) is confi gured by the 3-pin jumper.
Both are not available at the same time (RS485 / tLAN protocols).

2.9 Valve control

max power input for each valve
valve type
valve connector pins
power supply
max current
minimum winding resistance
maximum cable lenght
Note:
the UPC*****M* model can manage two diff erent valves. The 2 valves cannot run simultaneously but
in sequence;
only one valve can be connected to each connector;
the step frequency is selected by software;
select the right valve to heve better performances.
power supply distance
10 m
200 m
7 W
single-pole stepper
6
12 Vdc ±10%
0.3 A for each winding
40 Ω
2 m without shield-cable
6 m with shielded cable connected to ground both on
valve side and electronic controller side (E2VCABS3U0,
E2VCABS6U0)
power supply
μPC
taken from the
(150 mA)
μPC
taken from the
(150 mA)
7
ENG
Tab. 2.e
Tab 2.f
+050001570 - 1.2 - 22.06.11