Technical Data - S+S Regeltechnik PREMASGARD ALD Operating Instructions, Mounting & Installation

Measuring transducers for atmospheric pressure, calibrateable, with active output
Hide thumbs Also See for PREMASGARD ALD:
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 6
G
®
PREMASGARD
PREMASGARD
®
ALD measures the atmospheric pressure within a range of 850 - 1150 mbar and converts it into a standard signal
of 0 -10 V or 4 ... 20 mA respectively. The sensor system is designed for measurements in clean air and other non-aggressive,
non-condensing gaseous media. Applications of this pressure sensor are for example in ventilation and air conditioning technology,
air pressure dependent control systems, meteorological measurement stations and climate observation units. The pressure sensor
excels by its high accuracy, long-term stability and reliability. A device variant with additional display for pressure reading is available.

TECHNICAL DATA:

Power supply: ........................ 5 ... 36 V DC at I -variant
Output signal: ........................ 0 -10 V or 4 ... 20 mA
Current consumption: .............. max. 20 mA (at 24 V DC)
Electrical connection: .............. 2- or 3-wire connection
Medium: ............................... clean air and other non-aggressive, non-combustible gases
Type of pressure: .................... atmospheric pressure ⁄ absolute pressure
Measuring range: .................... 850 - 1150 mbar / 750 - 1250 mbar (selectable via DIP switches)
Max. pressure: ....................... 2000 mbar
Accuracy: .............................. ± 1.5 % of final value (at 20°C)
Long-term stability:................. ± 0.5 % of final value per year
Linearity: .............................. ± 0.5 % of final value
Temperature drift values: ......... ± 0.5 % of final value per 10 K
Hysteresis: ............................ ± 0.1 % of final value
Ambient temperature: ............. - 10 ... + 50 °C
Operating range: .................... 10 ... 95 % r.H.
Storage temperature: .............. - 20 ... + 50 °C
Turn-on time: ......................... < 1 min
t
: ..................................... 0 s ⁄ 1 s ⁄ 5 s ⁄ 10 s (selectable via DIP switches)
90
Enclosure: ............................. plastic, material polyamide, 30 % glass-globe-reinforced,
Enclosure dimensions: ............. 72 x 64 x 37.8 mm (Thor III without display)
Cable gland: ........................... M 16 x 1.5 ; including strain relief, exchangeable,
Electrical connection: .............. 0.14 - 1.5 mm², via terminal screws
Humidity: .............................. < 95 % r.H., non-precipitating air
Protection class: .................... III (according to EN 60 730)
Protection type: ..................... IP 65 (according to EN 60 529)
Standards: ............................ CE conformity, electromagnetic compatibility
Features: .............................. illuminated single line display, cutout 36 x15 mm (W x H)
Type ⁄ WG2
ALD - I
A L D - I
A L D - I - DI S P L AY
ALD - U
A L D - U
A L D - U _ DI S P L AY
Conversion table for pressure values:
Unit
=
1 Pa
1 kPa
1 bar
1 mbar
1 mH
O
0.0980665 bar
2
ALD
24 V AC (half-wave rectification) at U -variant
with quick-locking screws (slotted ⁄ Phillips head combination),
colour pure white (similar RAL 9010), enclosure cover for display is transparent!
72 x 64 x 43.3 mm (Thor III with display)
max. inner diameter 10.4 mm
according to EN 61 326 + A1 + A2, EMC directive 2004 ⁄ 108 ⁄ EC
indicating atmospheric pressure ⁄ absolute pressure
Measuring Range (adjustable)
850 - 1150 mbar ⁄ 750 - 1250 mbar
850 - 1150 mbar ⁄ 750 - 1250 mbar
850 - 1150 mbar ⁄ 750 - 1250 mbar
850 - 1150 mbar ⁄ 750 - 1250 mbar
bar
0.00001 bar
0.01 mbar
0.01 bar
10 mbar
1 bar
1000 mbar
0.001 bar
98.0665 mbar
Output
4 ... 20 mA
4 ... 20 mA
0 - 10 V
0 - 10 V
mbar
Pa
1 Pa
1000 Pa
100000 Pa
1 mbar
100 Pa
9806.65 Pa
Display
Item No.
I - variant
1301-1152- 0080- 100
1301-1152- 1080-100
U - variant
1301-1151- 0080- 100
1301-1151- 1080-100
kPa
0.001 kPa
0.000101971 mH
1 kPa
0.101971 mH
100 kPa
10.1971 mH
0.1 kPa
0.0101971 mH
9.80665 kPa
mH
O
2
O
2
O
2
O
2
O
2
1 mH
O
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents