Set Language (default: English), System Parameters, and Battery Parameters.
1. The preset password is 000001, used to enter the Settings menu.
2. The default feature code is 999999, used to restore the preset password.
Setting the Input Power Limiting
7.3
Choose Settings > Battery Parameters, and set Input
power limiting based on the actual situation. Default
value: 5 kW, value range 0.1–10 kW.
When installing a generator when a power failure occurs,
refer to section 10 and reset Input power limiting to the
maximum output capacity of the generator, and
automatically control the battery charge power to avoid
exceeding this limit.
Reset the AC input circuit breaker if its capacity is less than
75 A. The value is the circuit breaker capacity (A) x 100 V x
80%/1000.
If you set Input power limiting to an excessively smaller value, batteries are not charged, and
this may cause faults.
Note that if you set Input power limiting to an excessively larger value, the value may exceed
the capacity of the AC input circuit breaker.