TEMPERATURE MONITORING DEVICE COMEM DTI AND COMEM EDTI - INSTRUCTION MANUAL
18
6. Programming of the device

6.11 Configuration diagnostic probes

This function allows to enable or to disable the control on the
probes. This functionality controls the variation of the
temperature in a defined time. A flag raise if this variation is
higher than a set value.
FDC setting
FDC mode disabled
FDC mode enabled
It's necessary to indicate the maximum variation temperature:
• FDC: min 5°C or max 30°C
and after the time in which to do the control:
• FDC: min 10" or max 90" (time in seconds)
The ⇒+ key is used to increase the values while the ⇐- key to
decrease.
Confirm with ENTER.
Temperature configuration FDC
Min °C
Max °C
Time configuration FDC
Min in seconds
Max in seconds

6.12 Exit from the programming phase

Press the SET key or wait for about 8 seconds without to press
any key to come out of the programming phase.
T1-T2 display
FDC
FDC
T1-T2 display
FDC
FDC
T1-T2 display
FDC
FDC
T3-T4 display
Off
ON
T3-T4 display
-5°
30°
T3-T4 display
10''
90''