Technical Features - ABB Comem DTI Instruction Manual

Temperature monitoring device
Table of Contents

Advertisement

TRANSFORMER COMPONENTS

13. Technical features

Auxiliary power supply
Maximum consumption
Measured inputs
Interval of measure
Interval of visualization
Tripped delay-hysteresis
Measured visualization
Outputs
Output functions
programmable functions
Connection
Insulation
Protection degree
Dimensions – enclosure
Working temperature
Storing temperature
Standards
Management software for
Comem eDTI
24/230 V dc/ac ±15% 50-60 Hz
4 VA
3 - 4 inputs by RTD PT100
(max wire resistance 20 Ω)
-30°C up to +200°C / precision ± 2°C
-30°C up to +220°C
5 seconds – 2°C
2 displays with led 7 segments, 3-digits
Comem DTI: 4 relay NO-C-NC (250 V 5 A resistive
load)
Comem eDTI: 4 relay NO-C-NC (250 V 5 A resistive
load),
0-20 mA or 4-20 mA (Default); Modbus RTU
alarm, trip, fan, auto-diagnostic
ALARM, TRIP, HOLD, FAN, T.MAX, HOT, FDC
Extractible terminal with screws, section
wires max 2.5 mm
2
2500 Vrms 50 Hz per 60 s :U aux - input PT100 /
U aux - relay outputs / inputs PT100 - relay
outputs
IP52 front panel, IP20 rear panel, as CEI-EN 60529
Flash mounting DIN 96x96 mm, depth 120 mm /
Enclosure thermoplastic self-extinguishing as
UL94 V0
-10°C up to +60°C, humidity max 95%
-25°C up to +70°C
Security: EN 61010-1
EMC: EN 61000-4-2; EN 61000-4-3; EN
61000-4-4; EN 61000-4-5; EN 61000-4-11;
EN 61000-6-4
Available in our Download section at www.
abb.com/transformercomponents
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Comem edti

Table of Contents