Panasonic Urban Multi MX1 Series Manual page 62

Hide thumbs Also See for Urban Multi MX1 Series:
Table of Contents

Advertisement

Installation 2
No Setting item
Description
1
EMG
Emergency operation
(Emergency
when Inverter type
operation 1)
outdoor unit malfunctions.
2
Cool/heat
Address for cool/heat
unified
unified operation
address
3
Low noise /
Address for low noise
demand
/ demand operation
address
4
Forced fan
Indoor unit fan turns
switch
while unit is stopped.
5
Indoor unit
Allows operation of
forced
indoor unit from
operation
outdoor unit
Fixes compressor frequency.
6
Frequency fix
INV : (60Hz + OFF)
STD 1 : (ON+OFF)
STD 2 : (ON+OFF)
7
TE setting
Low pressure setting
for cooling
8
TC setting
High pressure setting
Note 1
for heating
9
Defrost
Temperature setting
setting
for defrost
Note 1
10
Air Net
Address for
address
Air Net
Initial setting (EMG)
62
LED display
H1P H2P H3P H4P H5P H6P H7P
S
S
S
S
Push 3 times
S
S
S
S
Push 3 times
S
S
LED display
H1P H2P H3P H4P H5P H6P H7P
Emergency operation
R
Normal operation
Address
0
Binary number
1
R
(6 digits)
2
31
Address
0
Binary number
1
R
(6 digits)
2
31
Forced fan operation
R
(H tap)
Normal operation
Forced fan operation
(H tap)
R
Normal operation
Frequency fix
R
Normal operation
High
R
Normal (factory set)
Low
R
Quick defrost
R
Normal (factory set)
Slow defrost
Address
0
Binary number
1
R
(6 digits)
2
63
PACD011001G2 / PACD011004G3
LED display
H1P H2P H3P H4P H5P H6P H7P
R
S
S
R
S
S
S
S
R
S
S
S
R
S
S
R
S
R
S
S
R
S
S
R
S
S
S
R
S
S
S
RETURN BUTTON
R
SET BUTTON
S
Urban Multi Inverter "MX1" Series
R
R
R
R
R
R
R
R
R
(V1828)