Installation 1
WHEN ELECTRIC WIRING WORK IS FINISHED
Check drainage flow during COOL running, explained under "TEST OPERATION".
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
Remove the electric parts box lid, connect a power supply and remote controller to the terminals.
Next, press the inspection/test operation button "
test operation mode. Press the operation mode selector button "
"
that the water has drained from the unit. Press "
Small Duct Type
1. Install the drain pipes.
(CS-JM)
30
". Then, press the ON/OFF button "
Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the
pipe.
Keep pipe size equal to or greater than that of the connecting pipe. (vinyl pipe of 26 mm nominal diam.).
Use the attached clamp and drain hose.
Tighten the clamp firmly.
Insulate the clamp with the attached sealing pad.
Insulate the drain pipe inside the building.
Drain piping may be clogged with dust and may result in water leakage and property damage.
When obliged to install the indoor units in a dusty place, cover the drainpan by field supplied to prevent
dust from falling into it.
While installing indoor units, take care that dust etc. should not drop into the drainpan.
It is nessesary to clean the drainpan.
PACD011001G2 / PACD011004G3
" on the remote controller. The unit will engage the
" until selecting FAN OPERATION
". The indoor unit fan and drain pump will start up. Check
" to go back to the first mode.