PACD011001G2 / PACD011004G3
( HOW TO INSTALL PIPING )
(1) Connect the drain pipe (field supplied) to the drain pipe, and insulate them.
(2) Connect the drain pipe to the drain outlet on the indoor unit, and tighten it with the clamp.
(3) Insulate both metal clamp and drain hose with the attached sealing pad.
2. After piping work is finished, check drainage flows smoothly.
Urban Multi Inverter "MX1" Series
To ensure a downward slope of 1:100, install hanging bars every 1 to 1.5 m.
If unifying multiple drain pipes, install pipes shown below.
Open the water inlet lid, add approximately 1000cc of water gradually and check drainage flow.
Watering can
Drain Pan
(V1879)
Installation 1
31