Siemens S120 PM240-2 Manual page 20

For hi power units by omar lift
Table of Contents

Advertisement

Table 5 Technical data PM240-2, FSE(3 AC 380 V to 480 V ±10 %)
PM240-2 with integrated line filter
Output current
Rated current In
Base-load current IH
Peak current Imax (3s over 300s)
Peak current Imax (57+3s over 300s)
Type rating¹)
on basis of In
on basis of IH
Rated pulse frequency
Power loss
Cooling air requirement
Sound pressure level LpA (1m)
24 V DC supply
for the Control Unit
Rated input current²)
with integrated line reactor
Class J UL fuses
Rated current
NH fuses IEC 60947
Rated current
Circuit breaker type designation IEC 60947
Rated current
Resistance value
ext. braking resistor
Max. cable length
to braking resistor
Line supply connection
L1, L2, L3
Tightening torque
Motor connection
U2, V2, W2
Tightening torque
DC link connection, connection for
braking resistor
DCP/R1, DCN, R2
Max. motor cable length ³)
shielded/unshielded
Degree of protection
Weight
with integrated line filter
¹) Rated power of a typical standard induction motor at 400 V 3 AC
²) The input current depends on the motor load and line impedance. The input currents apply for a load with
the type rating (based on I
³) Max. motor cable length 200 m (shielded) for PM240-2 Power Modules with integrated line filter to
maintain the limit values of EN 61800-3 Category C2.
3-12
code
) for a line impedance corresponding to uk = 1%.
n
6SL3210
1PE28-8AL0
A
90
A
75
A
150
A
113
kW
45
kW
37
kHz
4
kW
1.20
m³/s
0.083
dB
71
A
1.0
A
86
A
125
3NA3832
A
125
3VL1716-1DD33-
A
0AA0
125 ... 160
Ω
10
m
15
Screw terminals
2
25...70mm
10 Nm 88.5 lbf in
10,00...35,00mm
(AWG8... AWG2)
m
200/300
IP20
kg
28
Siemens PM240-2_EN_rev00-30082019.docx
1PE31-1AL0
110
90
180
135
55
45
4
1.55
0.083
71
1.0
104
150
3NA3836
160
3VL3720-1DC36-
0AA0
160 ... 200
(6 ... 3/0 AWG,)
2

Hide quick links: