Installation And Connection; Assembling The Amplifier; Connecting The Amplifier; Electrical Connection - Balluff IO-Link BAE SA-CS-027-YI-BP00,3 GS04 User Manual

Table of Contents

Advertisement

Available languages

Available languages

BAE SA-CS-027-YI-BP00,3 GS04
IO-Link Sensor Amplifier
5

Installation and connection

5.1

Assembling the amplifier

The following fitting methods are available:
Simple clamp fitting on the hat rail acc. to DIN, 35 mm
or 15 mm
Screw fixing with pan-head M3 screws
5.2

Connecting the amplifier

The amplifier can be operated with type BCS...-XXS-...
sensors.
Fig. 5-1:
Connecting the sensor
5.3

Electrical Connection

1
2
4
3
Fig. 5-2:
Plug layout (top view of M12 plug)
Pin Color
Signal
1
BN
L+ (Operating voltage +, SIO 10...30 V,
IO-Link 18...30 V)
2
WH
Teach line
3
BU
L− (Operating voltage −)
4
BK
C/Q output signal
Tab. 5-1:
Pin assignment
Teach-in mode is only useful in SIO mode.
In normal operation, the white teach line must
always be connected to the blue negative line.
www.balluff.com
5.4

SIO mode

PNP
BN
+
3
BK
OUT
BU
WH
ext. prog.
NPN
BN
+
3
BK
OUT
BU
WH
ext. prog.
Fig. 5-3:
SIO mode (PNP/NPN)
5.5

IO-Link operation

BN
1
+
3
BK
4
OUT
BU
3
WH
2
ext. prog.
Fig. 5-4:
IO-Link operation
+
1
4
3
2
+
1
4
3
2
+
C/Q
Master
english
9