FR1 Mounting Instructions

Step 1:
Lift the drive out from the carton and remove the
packaging. The magnetic cores and cable ties are
only included in EMI version drive.
Step 2:
Screw mounting: Attach the drive to the mounting
plate with two M5x20 (or 3/16 in.) screws and two
M5 (or 3/16 in.) nuts. The opening dimension on the
mounting plate should follow required dimensions
(refer to the dimension drawing in Table 1 of this
document).
DIN Rail mounting: Lift the drive at an angle about
30 degrees. Align the top hooks of drive DIN rail
mounting slot with DIN rail top edge. Push down and
rotate the drive to clip the bottom hooks on the bottom
DIN rail edge.
Step 3: (EMI version only)
Input wiring:
1P FR1 EMI version: Run the input wires (two line
wires+one grounding wire) through the input
magnetic core before connecting to the input terminal
block (L2/L3) and grounding hole. Tie the input
magnetic core to the input wires with a cable tie.
3P 230/480 V FR1 EMI version: Run the input wires
(three line wires + one grounding wire) through the
input magnetic core before connecting to the input
terminal block (L1/L2/L3) and grounding hole. Tie the
input magnetic core to the input wires with a cable tie
Output wiring:
All1P/3P FR1 EMI version: Run three motor wires
through the output magnetic core before connecting
to the output terminal block. The output grounding
wire should not run through the output magnetic core.
Tie the output magnetic core to the output wires with
a cable tie.
The maximum distance between the input/output
magnetic core's top surface is 100 mm (3.94 in.). All
EVM non-EMI version drives do not have
input/output magnetic cores.