Scaling the Analog Input Signal

Any two set points may be used to establish a response slope for the ASD. It is not necessary that the
two set points be at 0% and 100% of the feedback signal range.
Weak feedback signals can compensated for by adjusting the set points. For instance, if the feedback
signal for the voltage input terminal below were only 3 – 7 V, the same slope would be created by
entering the parameter pair settings F201-F202 and F203-F204 shown in Figure 10.
Figure 10. Example of voltage scaling to compensate for feedback amplitude.
8
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
80 Hz
F204
56 Hz
F202
24 Hz
0 Hz
0 V
3 V
F201
F203
0%
30%
70%
10 V
7 V
100%