Take care that the guide of valve rod top 08 should not fall out of cover 09
unchecked.
 Remove guide of valve rod top 08 from cover 09 and replace O-ring 39.
 Fit guide of valve rod top 08 in cover 09 and fit lock ring 40.
 Unscrew screw connection 24 and fit rod guide 05.
 Replace O-ring guide 23.
 Remove lock ring 25 and fit ring 06.
 Replace O-ring rod 22, remove ring 06 and fit lock ring 25.
 Fit rod guide 05 in guide valve rod top 08.
 Connect screw connection 24
 Remove compression spring 29.
 Remove suspension screw 03 from valve rod top 14;
 Remove retainer set 02 from bottom of connection rod 04.;
 Replace O-ring retainer set 21 and fit retainer set 02 to connection rod 04.
 Remove valve rod bottom 19 from valve rod top 14.
 Pull valve rod top 14 from valve 12 and replace O-ring 41.
 Re-insert valve rod top 14 in valve 12 and fix valve rod bottom 19 to valve rod top
14 (fix connection with LOCTITE 243).
 Replace filler block 01 of valve rod top 14.
 Fit connection rod 04 with retainer set 02 and suspension screw 03 back to valve
rod top 14 (fix suspension screw 03 with LOCTITE 243).
 Unscrew screw connection 31 and disconnect securing plate 13.
 Replace O-ring 30.
 Connect screw connection 31 (use new screws) and securing plate 13.
 Re-fit compression spring on valve.
 Slowly and carefully lower cover 09 with guide of valve rod top 08 over connection
rod 04. Work very carefully to prevent damage.
 Completely lower cover 09 with guide of valve rod top 08 over valve rod top 14.
 Slide coupling bottom 07b over connection rod 04 and fit retainer set 02 (with new
O-ring 21).
 Connect coupling bottom 07b to coupling top 07a (fix with a drop of LOCTITE 243)
and fit new filler block.
 Tighten connection rod 04 (figure 7a) and top of coupling 07a (fix connection with a
drop of LOCTITE 243).
 Unscrew screws 33 approx. 15 mm from valve seat 15.
 Screw load frame for M10 into tap thread holes of valve seat 15 provided for this
purpose.
 Slowly lift valve seat 15 from valve body 16 (with a suitable lifting tool).
 Check valve seat 15 for damage to the top sealing edge.
 Replace O-ring 32 and slowly and carefully mount valve seat 15 in the body of
valve 16.
 Again tighten screws 33 and remove load frame from valve seat 15.