Selftesting maintained/non maintained emergency luminaire with wireless communication

Advertisement

Package Contents
1
Luminaire
1
Mounting accessories
1
Manual
General
These devices are used indoors (ta 40 C) in places
o
is lower than the nominal, the BATTERY FAULT LED will
where emergency light is needed. Each device must
lit and battery needs to be replaced. If the result of the
be permanently connected to mains power supply.
test is good then the luminaire enters charging mode
In normal operation the battery is charging. The light
and the CHARGE LED starts blinking until the battery is
source can be either on or off, depending on user's
fully charged.
choice. In case of a mains power supply failure, the
device enters emergency mode and the illumination
Automatic Operational Test
LED turns on. When the mains power supply is
This test includes all the operations that are provided
restored the device turns to normal operation.
in Manual Operational Test and is conducted
automatically every 15 days and lasts 3 seconds.
Autonomy Duration Selection
The user can select one of the 3 available minimum
Automatic Autonomy Test
autonomy durations 1 hour, 3 hours and 8 hours. The
The Automatic Autonomy Test is conducted every 6
selection must be done while the luminaire is
months and measures the device's back up operation
disconnected from AC and battery supplies. The
and emergency duration. This test includes all
selection is achieved through Switches 2 & 3 of DS1
functions of the Manual Autonomy Test.
as shown below.
Wireless communication
The WL luminaire models have the ability to
communicate over the air with Olympia's control
panels for wireless emergency luminaires. The
1 2 3 4
1 2 3 4
1 2 3 4
luminaires can also communicate with a PC/laptop
1h
through a gateway (Ethernet, Wi-Fi, USB). For more
3h
8h
(default position)
information, please refer to Wireless Emergency
Lighting guides, available on the company's website.
Technical Label Installation
Two additional labels are included in the package.
one for 3 hours duration (180) and one for 8 hour
ΑΤΤΕΝΤΙΟΝ!!!
duration (480). Depending on the selected duration,
1. Operations for installation, maintainance or
the installer must cover the default 1 hour (60)
testing must be done by authorized personnel
printing with one label that has the required
only.
duration. Please take notice of the orientation of the
2. Always use in any case round mains cable, with a
label.
diameter of 5-10mm (H05RN-F type 2x1mm² or
any other type, at least equal to it's mechanical
Manual Operational Test
and electrical properties). ATTENTION!! The cable
Remove the diffusor and then by pressing the test
must not be deformed in any way (This
button briefly an operation test is initiated. The light
requirement is important to ensure the ΙΡ rating).
source and the emergency circuit of the device are
3. The device must be connected to the mains
tested. The manual test can be conducted only if the
power supply through a circuit breaker that is
mains power supply and the battery are connected.
depends on the total line's power load.
During this test period the LAMP TEST LED will blink.
4. In case of battery replacement, it must be
The battery must have adequate charge. This test
replaced by the same type, by the manufacturer
lasts for 3 seconds.
or a competent person.
5. In case of inactive use for a period greater than 2
Manual Autonomy Test
months, disconnect the battery by pulling out the
A duration test can be conducted by pushing the
battery's connector.
button steadily for 5 to 10 seconds. In order to be
6. I
t i
s not allowed to discard batteries into
performed, the mains power supply should be
common trash bins, they must be discarded
connected and the battery should be fully charged.
only
The luminaire enters emergency mode, the CHARGE
incinerate.
LED is turned OFF and the BATTERY FAULT LED starts
blinking. Its duration is the stated autonomy duration
of the luminaire. If at the end of the test the autonomy
Indications LED Status
LAMP
BATT.
CHARGE
Description
FAULT
FAULT
(green)
(red)
(yellow)
Charging
Fully charged
Battery fault or
emergency mode
Operational test
Light source fault
Autonomy test
Duration fault
1
Installation Instructions
1
3
2
1
4
Drill one of the available 5 holes with a 16-18mm drill bit. Install the included rubber gasket and pass
through the power cables. Install the included tie (if needed) to fasten and securely the power cables.
5
6) Autonomy Duration Selection
(Read on General Informations, Page 1)
6
7 b) Non-Maintained Operation
in battery recycling points. Do not
N
L
Ν for neutral, L for live wire WARNING!! Isolate the mains power supply before making the connections.
7
Battery Connection
Note:
Permanently
ON
Blink
Off
Indifferent
8
2
923102405_09_001
2
4
3
5
7 a) Permanent Maintained Operation
N
L
DS1
or
Link
Switch number 4 of DS1
must be in ON position.
Ν for neutral, L for live wire
WARNING!! Isolate the mains power supply before making the connections.
7
7 c) Controlled Maintained Operation of the lamp
N
L
External
and
switch
1 2 3 4
Switch number 4 of DS1
must be in OFF position.
8
9
10
A
Attention!! The 6 plastic latches (A) must be
A
secured (click sound). This requirement is
B
important to ensure the IP42 rating. Power on the
luminary.
11
Mounting Methods
Oly luminaires can be surface mounted on walls or ceilings. For these mounted installations, special
accessories are included.
Wall
bottom
Wall installation
view
1 2 3 4
Suspended installation with A-3018 accessory
The luminary can be installed in a suspended
ceiling.
Extra Mounting Methods *
and
1 2 3 4
* ATTENTION!!! The below mounting methods can be done after request of the necessary
Switch number 4 of DS1
mounting accessories!!
must be in OFF position.
A marking panel (SP-1100) can be installed on the luminary pointing the desired direction.
Ceiling installation
B
with marking panel
NOTE!!
A
After finishing the installation you must power the luminaire for at least 24 hours in order to
completely charge the battery. The rated autonomy duration can be achieved after that time.
3
923102405_09_001
A
A
A
A
A
A
Ceiling
Ceiling installation
Suspended ceiling installation
with mounting accessory
A-3018
Suspended ceiling installation
with mounting accessories
and marking panel
923102405_09_001