Sinclair SDV5 Series Service Manual page 72

Commercial air conditioners
Hide thumbs Also See for SDV5 Series:
Table of Contents

Advertisement

Step 6: Replace the faulty compressor and re-fit the other compressors
 Replace the faulty compressor.
 If the oil had been spoiled and was drained from the non-faulty compressor
in Step 3, use clean oil to clean them before re-fitting it into the unit. To
clean, add oil into the compressor through the discharge pipe using a funnel,
shake the compressor, and then drain the oil. Repeat several times and then
re-fit the compressors into the units. (The discharge pipe is connected to the
oil pool of the compressor by the inner oil balance pipe.)
Step 7: Add compressor oil
 Add oil to each of the compressors from which oil was drained in Step 3.
 Only use RB75EA oil. Different compressors require different types of oil.
Using the wrong type of oil leads to various problems.
 Add oil to the accumulator from which oil was drained in Step 4.
Step 8: Vacuum drying and refrigerant charging
 Once all the compressors and other components have been fully connected, vacuum dry the system and recharge
refrigerant.
Figure 6-2.6: Compressor piping
Discharge pipe
Suction pipe
71