Sinclair SDV5 Series Service Manual page 37

Commercial air conditioners
Hide thumbs Also See for SDV5 Series:
Table of Contents

Advertisement

Table 5-1.3: 100/120 model communication converter board PCB ports
Label in
Figure 5-1.3
1
2
3
4
5
Figure 5-1.4: 140/160 model outdoor unit Communication switchboard PCB Ports
Table 5-1.4: 140/160 model communication switchboard PCB ports
Label in
Port code
Figure 5-1.4
1
CN502
2
CN501
3
CN4
4
CN20
5
CN21
6
CN18
7
CN5
8
CN24
9
CN12
10
CN27
11
CN22
12
CN13
13
CN7
14
CN10
36
Port code
CN1
R T communication port
P Q E X Y E communication port(with main board)
CN2
CN3
O A communication port(reserved)
P Q E X Y E communication port
CN4
CN300
Chip burning port
Power input port
Power input port
Relay control/current sampling input port
Communication port between outdoor unit and indoor unit
Reserved
Outdoor unit heat exchanger pipe temperature/outdoor
environment temperature detection port
Compressor discharge temperature detection port
Compressor discharge temperature detection port
Signal input port of system low pressure & high pressure
detect switch
Online Programmable Port
EEV driving port
Load output port(4-way valve)
Reserved
Reserved
Content
Content
Port voltage
2.5-2.7V DC
2.5-2.7V DC
2.5-2.7V DC
2.5-2.7V DC
5V DC
Port voltage
AC 220V
AC 220V
DC 12V/AC 0-10.4V
DC 2.5~5V
/
DC 0~5V(in dynamic change)
DC 0~5V(in dynamic change)
DC 0~5V(in dynamic change)
DC 0~5V(in dynamic change)
DC 5V
The first pin: DC12V;
The other four pins: in dynamic change
AC 220
/
/

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sdv5-80easSdv5-100easSdv5-120easSdv5-140easSdv5-160eas

Table of Contents