2.11 EH: Refrigerant radiator temperature sensor error (For all models)
2.11.1 Digital display output
EH
2.11.2 Description
Refrigerant radiator temperature TL sensor error.
The system stops running.
Error code is displayed on outdoor unit PCB.
2.11.3 Trigger / recover condition
Trigger condition: TL temperature sensor is open circuited (or connecter loose) or short circuited.
Recover condition: The main control board can receive a normal feedback signal of TL sensor.
Reset method: Resume automatically.
2.11.4 Possible causes
TL temperature sensor damaged.
TL temperature sensor connect to the main control board is loose.
Main PCB damaged.
2.11.5 Procedure
Temperature sensor connection on main
Temperature sensor has short-circuited
Replace outdoor main PCB
2.12 EP: Outdoor ambient temperature is lower than -5
2.12.1 Digital display output
EP
2.12.2 Description
Outdoor ambient temperature is lower than -5℃ in cooling operation.
The system stops running.
Error code is displayed on outdoor unit PCB.
2.12.3 Trigger / recover condition
Trigger condition: Outdoor ambient temperature is lower than -5℃ in cooling operation.
Recover condition: Outdoor ambient temperature is over -5℃.
Reset method: Resume automatically.
2.12.4 Possible causes
EH
PCB is loose
No
or failed
No
Yes
Ensure the sensor is connected properly
Yes
Replace the sensor
in cooling operation (For all models)
℃
53