2.13.5 Procedure
Check LED301 Is
Check the wiring between main control
board and filter board is correct or not.
Voltage of power supply is 166-265V?
2.14 H0: Communicate malfunction between inverter module board and main control board (for all
models)
2.14.1 Digital display output
H0
2.14.2 Description
 Communicate malfunction between inverter module board and main control board protection.
 The system stops running.
 Error code is displayed on the unit with the error.
2.14.3 Trigger / recover condition
 Trigger condition: Communicate malfunction between inverter module board and main control board.
 Recover condition: Communicate between inverter module board and main control board is normal.
 Reset method: Resume automatically.
2.14.4 Possible causes
 DC fan motor damaged.
 The wire connect CN52 with CN53 is loose (100/120 model can ignore this reason for there's not this wire
connection).
 Main control board damaged.
 Filter board damaged (100/120 model can ignore this reason for they don't have a filter board).
F1
flashing or not
Yes
Yes
No
Replace outdoor main PCB
No
Connect again
No
Provide normal power supply