Display Operation
Display
ramming
k Meters
IOMM Starter
View parameters, messages and faults.
Shows software revision on power up.
Press PARAM to enter the menu and
then UP or DOWN to reach the desired
parameter.
Press ENTER to show the present value
of the parameter.
Press UP or DOWN to change the
parameter value.
Press ENTER to store the new value or
PARAM to abandon the change.
Press DOWN to display the motor
thermal overload content.
Press UP to display the incoming line
phase order.
Press ENTER to display the status
meter.
Log
Press PARAM, Select P24 and press
ENTER. The most recent fault will be
displayed as "xFyy" where x will be 1
to indicate the most recent fault is
being displayed and yy is the fault
code.
Press DOWN to view older faults. Up
to 9 faults may be stored in the log.
tting a Fault
First correct the cause of the fault.
Then press RESET to reset from a
fault.
tting Parameters
Press and hold PARAM and ENTER on
power up to reset parameters to
default values.
rgency Thermal Reset
Press RESET and DOWN to perform an
emergency thermal reset.