ELIS PLZEŇ a. s.
Here the value set by buttons ► and ▲ defines a zone of flow rate symmetric with respect to zero where
all outputs (current, OUT1 and OUT2 outputs, and the magnitude of instantaneous flow rate shown on the
meter display) indicate zero flow rate.
Any flow rate values greater than Suppressed flow rate will be correctly measured and indicated.
Return to Basic screen:
The suppressed flow rate value shall always be set in litres per second. Conversion of volume flow
rates in various units to flow rate in litres per second is described above in the procedure for setting
the 100% value.
The initial setting of the suppressed flow rate has been done by the manufacturer according to the
order number specification.
ELIS PLZEŇ a. s., Lucni 425/15, 301 00 Plzeň, Czech Republic tel.:+420 377 517 711, fax:+420 377 517 722
Project design, installation and service manual
Electromagnetic flowmeters of the type series
FLONEX FXx11x and FLONET FH30xx
Meter control instructions
ESC 2 s
Flow rates for various sensor sizes
DN
NPS
v = 0,025 m/s
½"
0,0036
15
¾"
0,0067
20
0,0100
25
1"
1 ¼"
0,0167
32
1 ½"
0,0250
40
2"
0,0400
50
2 ½"
0,0667
65
3"
0,1000
80
4"
0,1556
100
0,2389
125
5
6"
0,3611
150
8"
0,6389
200
10"
1,0000
250
12"
1,4000
300
14"
1,9444
350
16"
2,5000
400
20"
4,0000
500
24"
5,5556
600
7,7778
700
10,0000
800
12,7778
900
15,5556
1000
22,2222
1200
(l/s)
Q
Q
1
4
v = 10 m/s
1,8
3,33
5
8,33
12,5
20
33,33
50
77,77
119,44
180,55
319,44
500
700
972
1250
2 000
2 778
3 889
5 000
6 389
7 778
11 111
Page 26 o
33
f
Es 90 686 K