Fixed Current 4-20 Ma; Output Functions - Elis FLONEX FXx11x Series Control Instructions

Electromagnetic flowmeters
Table of Contents

Advertisement

ELIS PLZEŇ a. s.
5.1.4.3.3.
Fixed current 4–20 mA
Q− .. Q+
Output
Output
0 .. |Q|
Fixed current 4–20
ENTER
The flashing underline marker shows the digital position ready to be set.
Using buttons ► and ▲, set the highlighted current value in the range of 4 to 20mA. Confirm the setting by
depressing the ENTER button. The display will return to the previous menu item (Fixed current 4–20).
From that moment on the analog output is operated in the mode of fixed current. Return to the measuring
mode via setting the function of analog output.
Return to Main menu:
Return to Basic screen:
The value of fixed current can only be set within the range of 4.00 to 20.00mA. Values outside this
range will not be accepted; in that case, upon depressing button ENTER, the display will remain in
the mode of current setting and will not return to menu item Fixed current 4–20.
5.1.4.4.

Output functions

(passive, open collector)
The parameter setting procedures for Output 1 functions and Output 2 functions are the same.
Output 1 function
Output 2 function
Výěr položky
Function selection by buttons ► and ▲
To move upward in the menu,
use button ▲
ELIS PLZEŇ a. s., Lucni 425/15, 301 00 Plzeň, Czech Republic tel.:+420 377 517 711, fax:+420 377 517 722
Project design, installation and service manual
Electromagnetic flowmeters of the type series
FLONEX FXx11x and FLONET FH30xx
Meter control instructions
Fixed current 4–20
ENTER
mA
10.00
14.00
1 x ESC
ESC 2 s
Output 1 function
Function negation
ENTER
Frequency for Q+
Frequency for Q−
Frequency for |Q|
Impulses for Q+
Impulses for Q−
Impulses for |Q|
Constantly closed
Q>Qlim
|Q|>Qlim
No error
Output 1 function
ENTER
Frequency for Q+
To move downward in the menu, use
button
Page 17 o
33