Multidrive cabinets and modules
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Name
FSO-12 safety functions module user's manual
FSO-21 safety functions module user's manual

Multidrive modules

You can order a safety functions module from ABB. The cabinet builder can use the module
for implementing various safety functions.
Implementing the functions provided by the FSPS-21
PROFIsafe safety functions module

Cabinet-installed multidrives

You can order the drive with an FSPS-21 PROFIsafe safety functions module (option +Q986),
which provides PROFINET and PROFIsafe connection to the drive and has two safety
functions integrated into it: Safe torque off (STO) and Safe stop 1, time monitored (SS1-t).
With the module, it is possible to control the drive via PROFINET and safely stop the drive
via PROFIsafe.
The Safe torque off function can be controlled with PROFIsafe. When using FSPS-21
PROFIsafe safety functions module, other safety functions are not available. Use of
PROFIsafe and PROFINET is also possible by using FPNO-21 and FSO-xx option modules.
The settings of the module have default values when delivered from the factory. The wiring
and configuration of the FSPS-21 module are the responsibility of the user.
For more information, see FSPS-21 PROFIsafe safety functions module user's manual
(3AXD50000158638 [English]).

Multidrive modules

You can order the PROFIsafe safety functions module from ABB. The cabinet builder can
use the module for implementing following safety functions: Safe torque off (STO) and Safe
stop 1, time monitored (SS1-t).

Supplying power for the auxiliary circuits

Cabinet-installed multidrives
The drive can be equipped with an auxiliary voltage transformer (option +G344) and cooling
fan transformer(s) (option +G451). By default, they are supplied externally.
The user must supply these options from external power sources:
• +G300/+G301: Cabinet heaters and/or lighting (230 or 115 V AC; external fuse)
• +G307: Connection for an external uninterruptible power supply (230 or 115 V AC;
external fuse)

Multidrive modules

The cabinet installer must connect an auxiliary power supply for the drive. Auxiliary power
is needed, for example, by the control units and cabinet fan(s). See the appropriate hardware
manuals for the auxiliary power consumptions, connections, etc.
Electrical planning guidelines 39
Code
3AXD50000015612